| 2005-01-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) TABLE 403.1 MINIMUM FACILITIES |
| | INDICATE THAT 3 DRINKING FOUNTAINS ARE |
| | REQUIRED. PLANS INDICATE 2 SUPPLIED. |
| | ALSO SEE SECTION 410.1. |
| | 2) SUBMIT A DETAIL FOR DRINKING |
| | FOUNTAINS SHOWING COMPLIANCE WITH |
| | SECTION 11-4.15 AND ALL SUBSECTIONS. |
| | ALSO SHOW COMPLIANCE WITH SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| | HAVE DIFFICULTY BENDING OR STOOPING. |
| | 3) SUBMIT A DETAIL FOR THE KITCHEN AND |
| | BREAK ROOM SINKS. SHOW COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. A |
| | FORWARD APPROACH CLEAR FLOOR SPACE IS |
| | REQUIRED. |
| | 4) SUBMIT A DETAIL FOR THE URINALS |
| | SHOWING COMPLIANCE WITH SECTION 11-4.18 |
| | AND ALL SUBSECTIONS. |
| | 5) SUBMIT A DETAIL FOR THE SHOWER |
| | SHOWING COMPLIANCE WITH SECTION 11-4.21 |
| | AND ALL SUBSECTIONS. |
| | 6) SHT A-4 OF 14 SHOWS THE CLEAR FLOOR |
| | SPACE AS 36"X42". MIN. CLEAR FLOOR SPACE |
| | FOR SINKS IS 30"X48". SECTION 11-4.24.5. |
| | THE CLEAR FLOOR SPACE ALSO INDICATES THE |
| | CLEAR FLOOR SPACE AS A PARALLEL APPROACH |
| | WHEN A FORWARD APPROACH IS REQUIRED. |
| | 7) SHT A-5 OF 14 (SEE ABOVE COMMENT). |
| | 8) SHTS P-1 & P-2 SANT. RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN. NO HAND |
| | SINK IS SHOWN ON THE RISER DIAGRAM. |
| | 9) SHT P-2 WATER RISER DIAGRAM. FULL |
| | OPEN VALVES ARE REQUIRED ON TOP OF ALL |
| | WATER DOWN-FEED PIPES. SEE ROOM 120 AND |
| | JANITOR SINK BY STAIRS NEAR ROOM 120. |
| | 10) SHT P-2 WATER RISER AND SANT. RISER |
| | DIAGRAMS, THE P&T RELIEF LINES SHALL NOT |
| | DRAIN INTO FUNNEL FLOOR DRAINS. FLOOR |
| | DRAINS ARE NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. A FLOOR SINK OR A HUB |
| | DRAIN IS REQUIRED. SECTIONS 802.3 AND |
| | 802.3.2. |
| | 11) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR THE INSTA-HOT WATER HEATER SHOWN ON |
| | THE WATER RISER DIAGRAM SHT P-2. LISTING |
| | REQUIRED. SECTION 303.4. |
| | 12) A SEPARATE PERMIT AND PLANS ARE |
| | REQUIRED FOR THE IRRIGATION. PLUMBING |
| | CONTRACTOR SHALL INSTALL BACKFLOW FOR |
| | IRRIGATION. SECTION 104.3.1.1. |
| | |
| | |