| Plan Review Notes For Permit 04121254 |
| Permit Number |
04121254 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-05 00:00:00 | DENIED: | | | 1.PLAN SHEET A-8 DETAIL OF BUILDING | | | SECTION A SHOWS 2 HR RATED FLOOR/CEILING | | | ASSEMBLY UL #G350.THIS UL ASSEMBLY | | | NUMBER IS NOT SHOWN IN THE UL FIRE | | | RESISTANCE DIRECTORY. | | | | | | 2.PENDING THE ASSEMBLY OF THIS AREA, | | | FIRE DAMPERS AND RO RADIATION DAMPERS | | | MAY BE REQURIED. | | | | | | 3.PLEASE INDICATE WHAT TYPE OF WORK | | | AND STORAGE WILL BE IN THE WAREHOUSE | | | AREA AND AND THE DOOR SHOP AREA.PLEASE | | | INDICATE AND GASES, CHEMICALS OR | | | COMBUSTIBLES STORED OR USED IN THESE | | | AREAS. | | | | | | 4.PLEASE CLARIFY THE "WELDER" IN THE | | | "WOOD DOOR ASSEMBLY" AREA. | | | | | | 5.PLAN SHEET M-4 AHU HANGING DETAIL 1" | | | GALVENIZED DRAIN PAN, PER 2001 | | | FBC(M)307.2.3 AUXILIARY DRAIN PAN SHALL | | | BE A MINIMUM OF 1 1/2" DEEP AND NOT 1" | | | AS SHOWN ON THE PLAN. | | | | | | 6.PLAN SHEET M-4 INDICATES AHU HANGING | | | DETAIL SHOWS THE AHU SUPPORT TO THE | | | BOTTOM OF THE BAR JOIST.PROVIDE | | | ENGINEER LETTER AND MANUFACTURER'S | | | INSTALLATION SPECIFICATIONS SHOWING THIS | | | IS ACCEPTABLE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|