Plan Review Notes
Plan Review Notes For Permit 04121254
Permit Number 04121254
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-05 00:00:00DENIED:
 1.PLAN SHEET A-8 DETAIL OF BUILDING
 SECTION A SHOWS 2 HR RATED FLOOR/CEILING
 ASSEMBLY UL #G350.THIS UL ASSEMBLY
 NUMBER IS NOT SHOWN IN THE UL FIRE
 RESISTANCE DIRECTORY.
  
 2.PENDING THE ASSEMBLY OF THIS AREA,
 FIRE DAMPERS AND RO RADIATION DAMPERS
 MAY BE REQURIED.
  
 3.PLEASE INDICATE WHAT TYPE OF WORK
 AND STORAGE WILL BE IN THE WAREHOUSE
 AREA AND AND THE DOOR SHOP AREA.PLEASE
 INDICATE AND GASES, CHEMICALS OR
 COMBUSTIBLES STORED OR USED IN THESE
 AREAS.
  
 4.PLEASE CLARIFY THE "WELDER" IN THE
 "WOOD DOOR ASSEMBLY" AREA.
  
 5.PLAN SHEET M-4 AHU HANGING DETAIL 1"
 GALVENIZED DRAIN PAN, PER 2001
 FBC(M)307.2.3 AUXILIARY DRAIN PAN SHALL
 BE A MINIMUM OF 1 1/2" DEEP AND NOT 1"
 AS SHOWN ON THE PLAN.
  
 6.PLAN SHEET M-4 INDICATES AHU HANGING
 DETAIL SHOWS THE AHU SUPPORT TO THE
 BOTTOM OF THE BAR JOIST.PROVIDE
 ENGINEER LETTER AND MANUFACTURER'S
 INSTALLATION SPECIFICATIONS SHOWING THIS
 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.