| 2005-01-05 00:00:00 | ********** UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE NOTE ON PLANS |
| | MENTIONS WIND LOADING FOR LT POLES AND |
| | FIXTURES TO BE PROVIDED BY CONTRACTOR. |
| | THIS SI REQUIRED AT THIS TIME AND TO BE |
| | A PART OF THIS PLAN REVIEW PROCESS. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | PLEASE SEE 700.12E FOR CIRCUTING OF |
| | EM/EXT LTS. PANEL SCHEDULE INDICATES |
| | EM/EXT LTS ON INDIVIDUAL CIRCUIT.THE |
| | BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 3)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | WHICH ALSO REQUIRES THE PRINTED ANEM OF |
| | THE ENGINEER ON TITLE BLOCK. |
| | |
| | 4)NOTE:PLEASE SEE 600.5 FOR REQUUIRED |
| | SIGN CIRCUIT.EACH COMMERCIAL BUILDING |
| | AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE |
| | TO PEDESTRIANS SHALL BE PROVIDED WITH AT |
| | LEAST ONE OUTLET IN AN ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE TO EACH TENANT |
| | SPACE FOR SIGN OR OUTLINE LIGHTING |
| | SYSTEM USE. THE OUTLET(S) SHALL BE |
| | SUPPLIED BY A BRANCH CIRCUIT RATED AT |
| | LEAST 20 AMPERES THAT SUPPLIES NO OTHER |
| | LOAD. SERVICE HALLWAYS OR CORRIDORS |
| | SHALL NOT BE CONSIDERED ACCESSIBLE TO |
| | PEDESTRIANS. |
| | |
| | PLEASE REMOVE ALL OLD/ VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |