Plan Review Notes
Plan Review Notes For Permit 04121254
Permit Number 04121254
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-05 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS WIND LOADING FOR LT POLES AND
 FIXTURES TO BE PROVIDED BY CONTRACTOR.
 THIS SI REQUIRED AT THIS TIME AND TO BE
 A PART OF THIS PLAN REVIEW PROCESS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUTING OF
 EM/EXT LTS. PANEL SCHEDULE INDICATES
 EM/EXT LTS ON INDIVIDUAL CIRCUIT.THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 3)NOTE: PLEASE SEE FAC 61G15-23.002,
 WHICH ALSO REQUIRES THE PRINTED ANEM OF
 THE ENGINEER ON TITLE BLOCK.
  
 4)NOTE:PLEASE SEE 600.5 FOR REQUUIRED
 SIGN CIRCUIT.EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE
 TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING
 SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]