| 2005-01-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04121254 |
| | ADD: 1318 MERCER AVE |
| | CONT: SOUTHERN CONSTRUCTION |
| | TEL: (561)718-8876 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES |
| | BETWEEN THE LOTS WHICH COMBINE TO FORM |
| | 'THE SITE'.A 'UNITY OF TITLE' SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. |
| | SUBMIT A COPY OF THE RECORDED 'UNITY OF |
| | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 |
| | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | IT MAY REQUIRE REPLATTING, SINCE THE |
| | SURVEY INDICATES 6 LOTS THAT WOULD |
| | REQUIRE COMBINING INTO ONE LOT. |
| | |
| | 2) FBC* 105.3RESIDENT INSPECTOR. |
| | SUBMIT INSPECTOR RESUME' AND LICENSE |
| | DOCUMENTS TO HAROLD PISKURA (805-6711), |
| | DIRECTOR OF THE RESIDENT INSPECTOR |
| | PROGRAM.A RESIDENT INSPECTOR PROGRAM |
| | IS REQUIRED, ON THIS PROJECT, DUE TO ONE |
| | OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION. |
| | |
| | 3) SINCE THIS BUILDING REQUIRES A |
| | SPECIAL INSPECTOR, SUBMIT (3) SETS OF |
| | ALL DOCUMENTS, PLANS, REPORTS, PRODUCT |
| | APPROVALS, LETTERS AND OR SUBMITTALS . |
| | |
| | |
| | 4) SUBMIT A THIRD SET OF ENERGY |
| | CALCULATIONS. |
| | |
| | 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | A SINGLE SIGNED & SEALED REPORT WAS |
| | SUBMITTED, (3) ORIGINAL SIGNED AND |
| | SEALED REPORTS ARE REQUIRED. |
| | |
| | 6) THE PLANS SUBMITTED FROM BUTLER |
| | MANUFACTURING COMPANY SHALL REQUIRE THE |
| | PLANS TO BE SIGNED WITH ORIGINAL |
| | SIGNATURE OF THE P.E., ALL 3 SETS NOT |
| | COPIES OF SIGNATURES.SIGNED & SEALED. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 7) SEE SHEETS A-2.1 & A-3 FOR REQUIRED |
| | CLEARENCES AT THE PULL SIDE DOORS: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 8) A2.2 ROOF RACK HEIGHT SEE: |
| | 1511.7 ROOF MOUNTED MECHANICAL UNITS |
| | SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| | ARE EXPOSED TO WIND SHALL BE DESIGNED |
| | AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | |
| | 9) FBC* F102.2.7ARCHITECTURAL TRIM, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL BE CONSTRUCTED OF APPROVED |
| | NON-COMBUSTIBLE MATERIALS OR FIRE |
| | RETARDANT TREATED WOOD.ANNOTATE THE |
| | PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 10A) SHEET A-8 PROVIDE U.L. LISTING# |
| | G350 FOR A 2 HR FLOOR/ CEILING ASSEMBLY |
| | NOT IN 2004 LISTINGS. |
| | 10B) THE SAME SHEET MISSING WALL DESIGN |
| | U.L. LISTING# U-465 FOR A (2)HR RATING, |
| | U.L. INDICATES A 1 HR RATING. |
| | |
| | 11) A-9 STEEL BEAM PROTECTION PROVIDE |
| | THE U.L. LISTING FOR N306 , NOT IN 2004 |
| | |
| | LISTING BOOK. |
| | |
| | 12) TABLE 600 ISSUES SEE TYPEIV BLDG |
| | UNPROTECTED, FOOTNOTE (E) UNDER ROOF & |
| | ROOF CEILING ASSEMBLIES. ONLY FIRE |
| | RETARDANT TREATED WOOD CAN BE USED FOR |
| | SHEATHING ON BUILDINGS 2 STORIES OR |
| | LESS. SEE SHEET S0.2 NOTES PLYWOOD ROOF |
| | DECKING, ALSO S2.1 SECTION 5&6 PLEASE |
| | ANNOTE PLANS. |
| | |
| | 13) S-2.1 DETAIL# 4, ADD INFORMATION AS |
| | WHAT TYPE OF MATERIAL IS USED ON THE END |
| | OF THE GIRDER TRUSS. |
| | |
| | 14) SHEET S4.0 HEADER FOR PREENGINEERED |
| | |
| | METAL BUILDING DESIGN BASIS- MISSING |
| | WHAT BUILDING CODE DESIGNED UNDER? |
| | |
| | 15)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 16) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 3 COPIES OF THE |
| | PRODUCT APPROVAL FOR THRESHOLD OR |
| | RESIDENT INSPECTOR PROGRAM BUILDING. |
| | |
| | 17) PROVIDE THE PALM BEACH COUNTY IMPACT |
| | FEE RECEIPT, PART OF PERMIT PACKAGE |
| | REQUIREMENTS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |