| Date |
Text |
| 2004-12-30 00:00:00 | *************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE PLANS WHICH ARE |
| | SIGNED AND SEALED BY THE ENGINEER ARE |
| | REQUIRED TO HAVE A TITLE BLOCK WITH ALL |
| | INFORMATION AS SET-FORTH IN FAC |
| | 61G15-23.002. PLEASE SEE ELECTRICAL |
| | PLANS DO NOT CONTAIN ANY TITLE BLOCK FOR |
| | ENG. |
| | PLEASE SEE ALL PLANS ARE REQUIRED TO |
| | HAVE THE PRINTED NAME AND SIAGNATURE OF |
| | PERSON RESPONSIBLE FOR PLANS/DESIGN. PER |
| | FBC 104.2.1 THIS IS REQUIRED ON ALL |
| | PLANS AND FOR ALL TRADES WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE MOST HAVE BEEN REDLINED ON |
| | PLANS FOR LOCATIONS REQUIRED. |
| | |
| | 3)NOTE: PLEASE CORRELATE PLANS WITH |
| | PANEL SCHEDULE AND LOAD CALCULATIONS FOR |
| | WATER HEATER, OVEN/RANGE AND DRYER. |
| | PLANS SHOW AS GAS AND ELECTRICAL WITH |
| | LOADS ACCORD. |
| | PLEASE SEE WATER HOWEVER SHOWS A LOAD OF |
| | 4500W ON A 20A CIRCUIT. |
| | PLEASE SEE 422.13, REQUIRES MIN RATING |
| | OF 125%. |
| | |
| | 4)NOTE: PLEASE VERIFY OCP FOR AHU #2, |
| | THIS SHOWS 60A OCP FOR 7.5KW UNIT. |
| | 424.3B REQUIRES A MIN 125% . MAX MAY BE |
| | 150% FOR OCP. |
| | |
| | 5 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS. |
| | |
| | 8)NOTE: PLEASE INDICATE PANEL AS MCB. |
| | 225.31,240.4B,ETC. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |