Plan Review Notes
Plan Review Notes For Permit 04121162
Permit Number 04121162
Review Stop E
Sequence Number 3
Notes
Date Text
2005-02-11 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE REVIEW WHICH WAS
 PASSED ON 2/3 HAS NOW BEEN REVOKED DUE
 TO CHANGES TO STATE APPROVED TRAILER.
  
 2)NOTE:PLEASE PROVIDE PLANS SIGNED,
 DATED AND SEALED FOR ALL NEW ELECTRICAL
 WORK BEING PERFORMED.
 PLEASE INLCUDED ALL CIRCUITING AND PANEL
 SCHEDULES.215.5
 PLEASE SEE 700.12E FOR EM/EXT LTS.
  
  
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]