| Plan Review Notes For Permit 04121162 |
| Permit Number |
04121162 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | SHT C-4 WATER & FIRE SERVICE CONNECTION | | | DETAIL, BACKFLOW SHALL BE THE SAME SIZE | | | AS THE WATER SERVICE PER TABLE 603.1 | | | FOOTNOTE D. | | | | | | SEPARATE IRRIGATION PLANS/PERMIT | | | REQUIRED. PLUMBING CONTRACTOR SHALL | | | INSTALL BACKFLOW FOR IRRIGATION SYSTEM. | | | SECTION 104.3.1.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|