Plan Review Notes
Plan Review Notes For Permit 04121162
Permit Number 04121162
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SHT C-4 WATER & FIRE SERVICE CONNECTION
 DETAIL, BACKFLOW SHALL BE THE SAME SIZE
 AS THE WATER SERVICE PER TABLE 603.1
 FOOTNOTE D.
  
 SEPARATE IRRIGATION PLANS/PERMIT
 REQUIRED. PLUMBING CONTRACTOR SHALL
 INSTALL BACKFLOW FOR IRRIGATION SYSTEM.
 SECTION 104.3.1.1.
  
  