| 2005-01-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04121162 |
| | ADD: TO BE DETERMINED |
| | CONT:CENTEX ROONEY |
| | TEL: (561)478-0381 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) F102.1* SALES TRAILER IS LOCATED IN |
| | A FIRE DISTRICT NO TYPE VI CONSTRUCTION |
| | IS ALLOWED. |
| | |
| | 2A)SOILS LETTER FROM TIERRA |
| | GEOTECHNICAL |
| | INDICATES SOME TYPE OF TESTING |
| | PREFORMED |
| | AT THE SITE TO DETERMINE THE MINIMUM |
| | SOIL BEARING CAPACITY, PROVIDE |
| | DOCUMENTATION.1804.2.2. |
| | 2B) THE CODE SECTION 1818 REFRENCED IN |
| | YOUR LETTER DEALS SOILS IN HIGH |
| | VELOCITY HURRICANE ZONES, THIS PROJECT |
| | ISN'T IN A HVHZ. |
| | |
| | 3) THE PLANS FOR THE SALES TRAILER ARE |
| | TO BE STATE APPROVED, STAMPED BY THE |
| | ATATE AND A ACCOMPANING LETTER FROM THE |
| | |
| | DCA. |
| | 3B) IS THIS BUILDING IS NEW OR IS THE |
| | BUILDING BEING MOVED? |
| | 3C) PLANS INDICATE ENVOKING RULLE 9B-72 |
| | |
| | WHICH IS UNDER THE 2001 FL CODE BUT THE |
| | |
| | WIND SPEEDS REFLECTA 130 MPH WIND |
| | SPEED. |
| | THE LOCATION OF TRAILER IS A 140 MPH/ |
| | 3 SECOND GUST WIND SPEED. |
| | 3D) PLANS ALSO INDICATE WINDOWS ARE NOT |
| | LARGE MISSLE IMPACT RESISTANT. GENERAL |
| | NOTES (12) STATEAS PER LOCAL |
| | JURISDICTION. |
| | 4) PLANS FROM THE MANUFACTURED BUILDING |
| | |
| | INDICATE ON THE FRONT PAGE UNDER |
| | FOUNDATION THAT "THESE BUILDING PLANS DO |
| | NOT CONTAIN FOUNDATION SUPPORTS AND TIE |
| | DOWN SYSTEM SDETAILS AND |
| | SPECIFICATIONS" |
| | THE DESIGNER OF RECORD SHALL DESIGN |
| | |
| | THE FOUNDATION AND TIE DOWNS AND |
| | INDICATE THE FOLLOWING ON THE PLAN: |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 5) THE PLANS WITH EXTERIOR STAIRS AND |
| | RAMP INDICATE THE 2001 FL CODE BUT |
| | NOTHING ABOUT RULE 9B-72 (29)(G) |
| | REQUIRES PRODUCT APPROVAL W/ FL COVER |
| | SHEET. STRUCTURAL COMPONENTS- RAILINGS. |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) STORM SHUTTERS |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |