| 2005-05-11 00:00:00 | ********** UNSAT 2ND REVIEW********* |
| | |
| | 1)NOTE: PLEASE SEE PLANS NOW BEING |
| | SUBMITTED FOR REVIEW WHICH SHOWS NEW |
| | GUEST/APT UNIT. |
| | PLEASE SUBMIT A RISER DIAGRAM SHOWING |
| | NEW PANEL BEING ADDED TO EXISTING |
| | SERVICE. |
| | PLEASE SEE 225.31-225.36 FOR PANEL/ |
| | MAINS ETC AT DETACHED BLDG. |
| | PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDGS. |
| | PLEASE INCLUDE PANEL SCHEDULE SHOWING |
| | ALL MIN CIRCUITING REQUIRED UNDER 2002 |
| | NEC. 210.11,220.16,210.52,210.52D ETC. |
| | PLEASE SEE 210.12 2002 NEC FOR ARC FAULT |
| | PROTECTION REQUIRED. |
| | PLEASE INCLUDE LOAD CALCULATIONS FOR |
| | ADDED LOAD TO EXISTING SERVICE AND LOAD |
| | CALCS FOR NEW 100A PANEL. |
| | 220.31,215.5 |
| | PLEASE CLARIFU IF THESE ARE ADDED LOADS |
| | OR ARE THESE LOADS MOVING FROM MAIN |
| | HOUSE? |
| | |
| | 2)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | REQUIRES THE PRINTED NDAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS. |
| | THIS WAS REQUESTED ON PREVIOSU REVIEW. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |