2005-05-11 00:00:00********** UNSAT 2ND REVIEW*********
  
 1)NOTE: PLEASE SEE PLANS NOW BEING
 SUBMITTED FOR REVIEW WHICH SHOWS NEW
 GUEST/APT UNIT.
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 NEW PANEL BEING ADDED TO EXISTING
 SERVICE.
 PLEASE SEE 225.31-225.36 FOR PANEL/
 MAINS ETC AT DETACHED BLDG.
 PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDGS.
 PLEASE INCLUDE PANEL SCHEDULE SHOWING
 ALL MIN CIRCUITING REQUIRED UNDER 2002
 NEC. 210.11,220.16,210.52,210.52D ETC.
 PLEASE SEE 210.12 2002 NEC FOR ARC FAULT
 PROTECTION REQUIRED.
 PLEASE INCLUDE LOAD CALCULATIONS FOR
 ADDED LOAD TO EXISTING SERVICE AND LOAD
 CALCS FOR NEW 100A PANEL.
 220.31,215.5
 PLEASE CLARIFU IF THESE ARE ADDED LOADS
 OR ARE THESE LOADS MOVING FROM MAIN
 HOUSE?
  
 2)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NDAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
 THIS WAS REQUESTED ON PREVIOSU REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  