| Plan Review Notes For Permit 04121040 |
| Permit Number |
04121040 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-10-08 18:51:58 | ** REDLINED PLANS ** | | | | | | 1) NOTE: RISER IS BACK TO INDICATING AN EQUIPMENT | | | GROUNDING CONDUCTOR FROM THE GUTTER TO THE FIRST MEANS | | | OF DISCONNECT WHICH IS PARALLELING THE NEUTRAL. | | | 250.6, 250.24 | | | | | | 2) NOTE: RISER INDICATES THE PANELS K1 AND K2 AS BOTH | | | BEING 250MLO, YET THE PANEL SCHEDULES FOR EACH OF THESE | | | SAME TWO PANELS ARE SHOWN AS 225AMP. | | | | | | | | | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|