Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop E
Sequence Number 9
Notes
Date Text
2009-10-08 18:51:58** REDLINED PLANS **
  
 1) NOTE: RISER IS BACK TO INDICATING AN EQUIPMENT
 GROUNDING CONDUCTOR FROM THE GUTTER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS PARALLELING THE NEUTRAL.
 250.6, 250.24
  
 2) NOTE: RISER INDICATES THE PANELS K1 AND K2 AS BOTH
 BEING 250MLO, YET THE PANEL SCHEDULES FOR EACH OF THESE
 SAME TWO PANELS ARE SHOWN AS 225AMP.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  