2009-09-24 08:09:18** DENIED **
  
  
  
 1) NOTE: PLEASE SUBMIT A REVISED RISER DIAGRAM TO
 COORDINATE WITH REVISED PANELS.
 PLEASE COORDINATE PANELS. AS REDLINED ON PREVIOUS PLANS
 PANEL K1 WAS NOT A 42 CIRCUIT PANEL IN FIELD HOWEVER
 PLANS ARE STILL THE SAME. HAS THE PANEL NOW CHANGED IN
 THE FIELD?
 IF THIS PANEL IS IN FACT A 30 CIRCUIT PANEL THEN ALL
 THE CIRCUITING ABOVE 30 ON THE SCHEDULE WOULD NOT BE
 CORRECT.
  
 2) NOTE: PLEASE SUBMIT THE REVISED RISER DIAGRAM SHEET.
 215.5,230, ETC
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  