| Plan Review Notes For Permit 04121040 |
| Permit Number |
04121040 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2009-09-24 08:09:18 | ** DENIED ** | | | | | | | | | | | | 1) NOTE: PLEASE SUBMIT A REVISED RISER DIAGRAM TO | | | COORDINATE WITH REVISED PANELS. | | | PLEASE COORDINATE PANELS. AS REDLINED ON PREVIOUS PLANS | | | PANEL K1 WAS NOT A 42 CIRCUIT PANEL IN FIELD HOWEVER | | | PLANS ARE STILL THE SAME. HAS THE PANEL NOW CHANGED IN | | | THE FIELD? | | | IF THIS PANEL IS IN FACT A 30 CIRCUIT PANEL THEN ALL | | | THE CIRCUITING ABOVE 30 ON THE SCHEDULE WOULD NOT BE | | | CORRECT. | | | | | | 2) NOTE: PLEASE SUBMIT THE REVISED RISER DIAGRAM SHEET. | | | 215.5,230, ETC | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|