2009-04-07 21:19:57** DENIED REVIEW **
  
 ** REDLINED PLANS.
  
 1) NOTE: RISER SHOWS A 150AMP BREAKER FEEDING PANEL
 K-1. THE RISER CONTAINS A NOTE WHICH STATES THE PANEL
 K-2 IS FED FROM KI BY A 250AMP BREAKER. EVEN IF THIS
 BREAKER IS PART OF A FEED-THRU BREAKER SCENARIO, THE
 FEEDERS FROM PANEL K ARE STILL ONLY RATED FOR 150AMPS
 AS THEY ARE 1/0 CONDUCTORS. WHY WOULD THERE BE 250MCM
 FROM PANEL K-1 TO K-2 WHEN THE CONDUCTORS FROM PANEL K
 ARE ONLY RATED FOR 150AMPS. THE LOAD ON PANEL K2 ALONE
 EXCEEDS THE RATING OF THE 150AMP FEEDERS.
 310.16, 240.4.
 220
  
 ** CALLED AND LEFT MESSAGE AT ELECTRICAL DESIGNER'S
 OFFICE AND CONTRACTOR PHONE NUMBER. PLANS MAY BE
 REDLINED FOR INSPECTIONS OF ELECTRICAL DEVICES ONLY
 INCLUDING LIGHTING HOWEVER IT WOULD NOT INCLUDE
 ELECTRICAL SERVICE EQUIPMENT UNTIL CORRECTIONS ARE
 MADE.