| Plan Review Notes For Permit 04121040 |
| Permit Number |
04121040 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2009-04-07 21:19:57 | ** DENIED REVIEW ** | | | | | | ** REDLINED PLANS. | | | | | | 1) NOTE: RISER SHOWS A 150AMP BREAKER FEEDING PANEL | | | K-1. THE RISER CONTAINS A NOTE WHICH STATES THE PANEL | | | K-2 IS FED FROM KI BY A 250AMP BREAKER. EVEN IF THIS | | | BREAKER IS PART OF A FEED-THRU BREAKER SCENARIO, THE | | | FEEDERS FROM PANEL K ARE STILL ONLY RATED FOR 150AMPS | | | AS THEY ARE 1/0 CONDUCTORS. WHY WOULD THERE BE 250MCM | | | FROM PANEL K-1 TO K-2 WHEN THE CONDUCTORS FROM PANEL K | | | ARE ONLY RATED FOR 150AMPS. THE LOAD ON PANEL K2 ALONE | | | EXCEEDS THE RATING OF THE 150AMP FEEDERS. | | | 310.16, 240.4. | | | 220 | | | | | | ** CALLED AND LEFT MESSAGE AT ELECTRICAL DESIGNER'S | | | OFFICE AND CONTRACTOR PHONE NUMBER. PLANS MAY BE | | | REDLINED FOR INSPECTIONS OF ELECTRICAL DEVICES ONLY | | | INCLUDING LIGHTING HOWEVER IT WOULD NOT INCLUDE | | | ELECTRICAL SERVICE EQUIPMENT UNTIL CORRECTIONS ARE | | | MADE. | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|