| 2009-01-30 13:34:31 | DENIED |
| | REFERENCE: |
| | FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | 1. PLANS WERE SUBMITTED AS A RESTAMP. THERE ARE CHANGES |
| | TO THE ORIGINAL PLANS AND THE ORIGINAL SET OF PLANS HAS |
| | 5 PLUMBING SHEETS WHEREAS THERE WERE ONLY 3 PLUMBING |
| | SHEETS. PLEASE SUBMIT ALL SHEETS. PER THE LETTER THERE |
| | IS A NEW ARCHITECT OF RECORD SO ALL SHEETS SHALL BE |
| | REPRODUCED BY THE NEW ARCHITECT OF RECORD. FAC |
| | 61G1-18.002. |
| | |
| | 2. SHT 3.0P THE FLOOR SINK FOR THE 3 COMPARTMENT SINK |
| | SHOWS NO CONNECTION TO THE BUILDING DRAIN OR BRANCH |
| | LINE. SECTION 701.1. PLEASE INDICATE WHERE THE FLOOR |
| | SINK CONNECTS TO THE SANITARY DRAINAGE. SECTION |
| | 104.2.1. |
| | |
| | 3. SHT 3.0P THE HOT WATER SUPPLY TO THE LAVS IN THE |
| | MEN'S & WOMEN'S TOILET ROOMS SHALL BE INDICATED ON THE |
| | LEFT SIDE OF THE FIXTURE. SECTION 607.4. PLANS SHOW HOT |
| | ON RIGHT SIDE OF FIXTURE. |
| | |
| | 4. SHT 3.2A NOTES NUMBER 3 INDICATES THE PLUMBING CODE |
| | AS 2004. THE CODE IN EFFECT AT THE TIME THE PERMIT WAS |
| | ISSUED WAS 2001. PLEASE CORRECT CODE REFERENCE. SECTION |
| | 104.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |