Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop P
Sequence Number 4
Notes
Date Text
2009-01-30 13:34:31DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. PLANS WERE SUBMITTED AS A RESTAMP. THERE ARE CHANGES
 TO THE ORIGINAL PLANS AND THE ORIGINAL SET OF PLANS HAS
 5 PLUMBING SHEETS WHEREAS THERE WERE ONLY 3 PLUMBING
 SHEETS. PLEASE SUBMIT ALL SHEETS. PER THE LETTER THERE
 IS A NEW ARCHITECT OF RECORD SO ALL SHEETS SHALL BE
 REPRODUCED BY THE NEW ARCHITECT OF RECORD. FAC
 61G1-18.002.
  
 2. SHT 3.0P THE FLOOR SINK FOR THE 3 COMPARTMENT SINK
 SHOWS NO CONNECTION TO THE BUILDING DRAIN OR BRANCH
 LINE. SECTION 701.1. PLEASE INDICATE WHERE THE FLOOR
 SINK CONNECTS TO THE SANITARY DRAINAGE. SECTION
 104.2.1.
  
 3. SHT 3.0P THE HOT WATER SUPPLY TO THE LAVS IN THE
 MEN'S & WOMEN'S TOILET ROOMS SHALL BE INDICATED ON THE
 LEFT SIDE OF THE FIXTURE. SECTION 607.4. PLANS SHOW HOT
 ON RIGHT SIDE OF FIXTURE.
  
 4. SHT 3.2A NOTES NUMBER 3 INDICATES THE PLUMBING CODE
 AS 2004. THE CODE IN EFFECT AT THE TIME THE PERMIT WAS
 ISSUED WAS 2001. PLEASE CORRECT CODE REFERENCE. SECTION
 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  