Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop E
Sequence Number 4
Notes
Date Text
2009-03-27 16:50:56** DENIED REVIEW **
  
 REVISION
  
  
  
 1) NOTE: PLEASE COORDINATE CALCULATIONS, PLANS, LIGHT
 FIXTURES AND FIXTURE LEGEND. COMPLIANCE CAN NOT BE
 VERIFIED AS THE 2X4 LAY IN FIXTURES FOR EXAMPLE ARE NOT
 SPECIFIC ON PLANS. THE SYMBOL LEGEND INDICATES ONLY ONE
 FIXTURE FOR THIS SYMBOL YET THE FIXTURE LEGEND
 INDICATES TWO SEPARATE FIXTURES. ONE FIXTURE CONSUMES
 TWICE THE WATTAGE OF THE OTHER.
 13-415.2
 ** IT IS IMPORTANT TO KNOW THAT CEILING FANS ARE NOT
 PERMITTED TO CONTAIN LIGHT FIXTURES OR KITS UNLESS PART
 OF THE CALCULATIONS.
  
 2) NOTE: THE DEVICE LEVELS FOR HORNS, STROBES ARE NOT
 ON SYMBOL LEGEND. THESE MUST MEET FBC 11-4.28.1, .2 AND
 .3.
 FS 633 REQUIRES THE BASE PLANS TO MEET REQUIRED DESIGN
 INTENT FOR ALL BUILDING CODE REQUIREMENTS INCLUDING
 NFPA-72.
 THE HEIGHTS WHICH WERE ADDED IS NOT THE ONLY THING
 REQUIRED.
  
 3) NOTE: PLEASE COORDINATE RISER AND ELECTRICAL PANELS.
 THE RISER SHOWS THE K2 PANEL BEING FED FROM K PANEL
 HOWEVER K PANEL SCHEDULE ONLY INDICATES ONE PANEL BEING
 FED WHICH IS THE K1 PANEL.
 K PANEL CAN NOT BE A FEED-THRU PANEL AS K IS 400AMP
 RATED AND K2 IS ONLY 250AMP RATED AND K IS FED BY
 400AMP OVER CURRENT PROTECTION.
 240.4, 310.16, 230.76, 110.3, ETC.
  
 4) NOTE: PLEASE SEE 310.16 AS THE RISER SHOWS 350MCM
 FEEDERS FROM THE 400AMP MCB DISCONNECT TO THE PANEL K.
 HOWEVER BASED ON 310.16, 110.14, THE 350MCM ARE ONLY
 RATED FOR 310AMPS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES THE NFPA-101 IN
 EFFECT AT THE TIME OF PERMIT APPLICATION IS THE 2000.
 PLANS STATE 2003 WHICH DID HAVE CHANGES TO EGRESS PATHS
 IN DESIGN.
  
 6) NOTE: A FORM 400C-04 WAS SUBMITTED AS PART OF THE
 PACKAGE FOR PRESCRIPTIVE REQUIREMENTS.
 THE FIRST ITEM WOULD BE THE FACT THE FORM WAS NOT
 SIGNED, DATED OR SEALED BY THE ARCHITECT LISTED.
 SECOND: THE FORM IS FROM THE 2004 FBC. PLANS ARE STATED
 TO BE UNDER THE 2001
 THIRD: THE FORM IS NOT COMPLETE.
 FORTH: THE FORM IS METHOD *C*, WHERE PLANS FOR LIGHTING
 ANYWAY MENTIONS SPACE BY SPACE WHICH IS *B*. PLEASE SEE
 THE CODE AS IT DOES NOT PERMIT THE USE OF TWO DIFFERENT
 METHODS FOR THE SAME SPACE/PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  