| Date |
Text |
| 2009-03-27 16:50:56 | ** DENIED REVIEW ** |
| | |
| | REVISION |
| | |
| | |
| | |
| | 1) NOTE: PLEASE COORDINATE CALCULATIONS, PLANS, LIGHT |
| | FIXTURES AND FIXTURE LEGEND. COMPLIANCE CAN NOT BE |
| | VERIFIED AS THE 2X4 LAY IN FIXTURES FOR EXAMPLE ARE NOT |
| | SPECIFIC ON PLANS. THE SYMBOL LEGEND INDICATES ONLY ONE |
| | FIXTURE FOR THIS SYMBOL YET THE FIXTURE LEGEND |
| | INDICATES TWO SEPARATE FIXTURES. ONE FIXTURE CONSUMES |
| | TWICE THE WATTAGE OF THE OTHER. |
| | 13-415.2 |
| | ** IT IS IMPORTANT TO KNOW THAT CEILING FANS ARE NOT |
| | PERMITTED TO CONTAIN LIGHT FIXTURES OR KITS UNLESS PART |
| | OF THE CALCULATIONS. |
| | |
| | 2) NOTE: THE DEVICE LEVELS FOR HORNS, STROBES ARE NOT |
| | ON SYMBOL LEGEND. THESE MUST MEET FBC 11-4.28.1, .2 AND |
| | .3. |
| | FS 633 REQUIRES THE BASE PLANS TO MEET REQUIRED DESIGN |
| | INTENT FOR ALL BUILDING CODE REQUIREMENTS INCLUDING |
| | NFPA-72. |
| | THE HEIGHTS WHICH WERE ADDED IS NOT THE ONLY THING |
| | REQUIRED. |
| | |
| | 3) NOTE: PLEASE COORDINATE RISER AND ELECTRICAL PANELS. |
| | THE RISER SHOWS THE K2 PANEL BEING FED FROM K PANEL |
| | HOWEVER K PANEL SCHEDULE ONLY INDICATES ONE PANEL BEING |
| | FED WHICH IS THE K1 PANEL. |
| | K PANEL CAN NOT BE A FEED-THRU PANEL AS K IS 400AMP |
| | RATED AND K2 IS ONLY 250AMP RATED AND K IS FED BY |
| | 400AMP OVER CURRENT PROTECTION. |
| | 240.4, 310.16, 230.76, 110.3, ETC. |
| | |
| | 4) NOTE: PLEASE SEE 310.16 AS THE RISER SHOWS 350MCM |
| | FEEDERS FROM THE 400AMP MCB DISCONNECT TO THE PANEL K. |
| | HOWEVER BASED ON 310.16, 110.14, THE 350MCM ARE ONLY |
| | RATED FOR 310AMPS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTES THE NFPA-101 IN |
| | EFFECT AT THE TIME OF PERMIT APPLICATION IS THE 2000. |
| | PLANS STATE 2003 WHICH DID HAVE CHANGES TO EGRESS PATHS |
| | IN DESIGN. |
| | |
| | 6) NOTE: A FORM 400C-04 WAS SUBMITTED AS PART OF THE |
| | PACKAGE FOR PRESCRIPTIVE REQUIREMENTS. |
| | THE FIRST ITEM WOULD BE THE FACT THE FORM WAS NOT |
| | SIGNED, DATED OR SEALED BY THE ARCHITECT LISTED. |
| | SECOND: THE FORM IS FROM THE 2004 FBC. PLANS ARE STATED |
| | TO BE UNDER THE 2001 |
| | THIRD: THE FORM IS NOT COMPLETE. |
| | FORTH: THE FORM IS METHOD *C*, WHERE PLANS FOR LIGHTING |
| | ANYWAY MENTIONS SPACE BY SPACE WHICH IS *B*. PLEASE SEE |
| | THE CODE AS IT DOES NOT PERMIT THE USE OF TWO DIFFERENT |
| | METHODS FOR THE SAME SPACE/PERMIT. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |