| 2009-02-01 14:20:32 | REVIEW #: REVISION - CHANGE OF DESIGNER |
| | ACTION: DENIED |
| | |
| | FBC 2001 CODE FAMILY |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. GENERAL NOTES INDICATE THIS PROJECT IS UNDER THE |
| | 2004 FBC. THIS PROJECT IS PERMITTED UNDER THE 2001 FBC. |
| | PLEASE ADJUST ALL PLAN NOTES AND DESIGN REQUIREMENTS |
| | ACCORDINGLY. |
| | |
| | 2. THESE PLANS WERE SUBMITTED AS A RESTAMP. HOWEVER, IN |
| | CONJUNCTION WITH THE CHANGES IN DESIGN PROFESSIONALS, |
| | THE HVAC SYSTEMS HAVE BEEN COMPLETELY REDESIGNED. THAT |
| | MEANS THESE PLANS CONSTITUTE A REVISION. PLEASE PAY ALL |
| | APPLICABLE FEES FOR A REVISION BASED ON THE CITY'S |
| | CURRENT FEE SCHEDULE. |
| | |
| | 3. THE RE-CREATED PLANS BY METRO ARCHITECTURE HAVE |
| | OMITTED THE COMMERCIAL KITCHEN EXHAUST SYSTEM. |
| | COMMERCIAL KITCHEN GREASE HOOD, GREASE EXHAUST DUCT AND |
| | ASSOCIATED VENTILATION SYSTEMS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH FBCM 506 AND 507. |
| | |
| | 4. SHOW HEIGHT OF ROOF STANDS TO BE IN COMPLIANCE WITH |
| | FBCB TABLE 1511.7. |
| | |
| | 5. NOTE ON PAGE 3.1A CALLS FOR DUCTS PENETRATING |
| | FLOOR/CEILING ASSEMBLY TO BE PROTECTED WITH "EXPANDING |
| | COLLARS." DUCTS CONNECTING MORE THAN 2 FLOORS SHALL BE |
| | ENCLOSED IN SHAFT CONSTRUCTION IN ACCORDANCE WITH FBCM |
| | 607 AND FBCB CHAPTER 7. DUCT PENETRATIONS OF SHAFT |
| | ENCLOSURES SHALL BE PROTECTED IN ACCORDANCE WITH FBCM |
| | SECTION 607. |
| | |
| | 6. NOTE ON 3.1A CALLS FOR SMOKE DETECTORS ON EACH AHU. |
| | THERE IS NO SMOKE DETECTOR SHOWN ON AHU 2 ON FLOOR |
| | PLAN. PLEASE CORRECT IN ACCORDANCE WITH FBCM 606. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |