Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2009-02-03 14:59:58***DENIED***
  
 1) PLEASE SEE MECHANICAL REVIEW COMMENT #3 REGARDING
 HOOD/SUPPRESSION SYSTEMS. IN ADDITION, SEPARATE SHOP
 DRAWINGS AND PERMITS REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) OCCUPANT LOAD SIGN IS REQUIRED PRIOR TO FINAL
 INSPECTION. CONTACT BUREAU OF FIRE PREVENTION AT (561)
 804-4724 FOR ASSISTANCE.
  
 4) PLEASE ADD NOTE FROM FIRST FIRE PLAN REVIEW ON DOOR
 SCHEDULE REGARDING PANIC HARDWARE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756