| 2009-01-16 10:50:23 | ** DENIED PLANS** |
| | |
| | |
| | ** PLANS SUBMITTED DO CONTAIN REVISIONS AND NOT ALL ARE |
| | A RE-STAMP. |
| | |
| | |
| | 1) NOTE: PROJECT IS UNDER THE 2001 FBC. PLEASE ADJUST |
| | CODES FOR OTHER AS WELL. |
| | DESIGN MAY STILL BE UNDER 2004 AS SHOWN, HOWEVER AS |
| | LONG AS THE DESIGN MEETS THE 2001 THIS IS THE CODE |
| | WHICH NEEDS TO BE PLACED ON THE PLANS. |
| | |
| | 2) NOTE: PLEASE COORDINATE ALL ITEMS ON THE PANELS WITH |
| | THE RISER DIAGRAM. THERE ARE SEVERAL ITEMS WHICH HAVE |
| | BEEN COMPLETELY REVISED FROM ORIGINAL PLANS AS WELL AS |
| | SEVERAL ITEMS WHICH DO NOT CORRELATE. |
| | RISER SHOWS 600AMP MAIN TO 600AMP MAIN PANEL. |
| | THIS PANEL IS NOTED AS PANEL *A* ON RISER YET PANEL *K* |
| | ON PANEL SCHEDULE. |
| | THIS PANEL IS ALSO 400AMP MLO ON SCHEDULE. |
| | PANEL *K* SCHEDULE DOES NOT INDICATE THE |
| | BREAKERS/CIRCUIT FEEDING BOTH PANELS AS SHOWN ON RISER. |
| | IN FACT THE RISER SHOWS ONE PANEL AS PANEL *C* WHICH IS |
| | 125AMPS AND PANEL *B* IS SHOWN AS 225AMP MLO. |
| | THERE IS IN FACT NO PANEL *C* OR *B* SCHEDULE EVEN |
| | SUBMITTED. THERE IS HOWEVER A NEW *K1*. |
| | |
| | ** THESE ITEMS AS NOTED ABOVE ARE A FEW EXAMPLES OF |
| | ITEMS WHICH DO NOT COORDINATE. PLEASE REVISE AND SHOW |
| | COMPLIANCE FOR ALL FEEDERS, OVER CURRENT PROTECTION, |
| | REVISED SCHEDULES, REVISED PANELS ETC. |
| | 240.4,310.16,408.4,250,230,225,215, |
| | |
| | 3) NOTE: PLEASE INCLUDE ALL HORN/STROBE LEVELS PER |
| | 11-4.28.1,.2 AND .3. |
| | |
| | 4) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY |
| | AND EXIT LIGHTS. THERE ARE SOME ON PLANS MISSING |
| | CIRCUITING. |
| | |
| | 5) NOTE: PLEASE SEE THE EGRESS PATHS ALONG THE BOOTHS |
| | DO NOT SHOW ANY EMERGENCY BACK UP LIGHTS. WHEN THIS |
| | PROJECT WAS ORIGINALLY PERMITTED THE REVIEW OF EGRESS |
| | LIGHTING WAS NOT UNDER THE ELECTRICAL REVIEW. THIS IS |
| | NOT PART OF THE ELECTRICAL REVIEW SO PLEASE REVISE TO |
| | MEET THE LIFE SAFETY CODE IN EFFECT AT THE TIME OF |
| | PERMIT APPLICATION. |
| | PLEASE SEE NFPA-101 2000, 7.8 AND 7.9. |
| | ** NOTED FOR INFORMATION: THE LIGHTING LEVELS FOR ALL |
| | EGRESS WALKING SURFACES WHICH ARE FLAT ARE THE SAME AS |
| | THE CURRENT CODES. ONLY STAIRS CHANGED IN THE 2003 LIFE |
| | SAFETY CODE. |
| | |
| | 6) NOTE: PLEASE PROVIDE OR REVISE THE SYMBOL LEGEND AS |
| | SUBMITTED. THERE ARE ITEMS ON PLANS WHICH CAN NOT BE |
| | DETERMINED AT THIS TIME. SEE DEVICE WHICH SEEMS TO BE |
| | HALF OF A HORN/STROBE WHICH IS SHOWN CIRCUITED TO A |
| | LIGHT FIXTURE. WHAT IS THIS? |
| | THERE ALSO SEEMS TO BE HORN/STROBES IN OTHER LOCATION |
| | CONNECTED TO EMERGENCY AND EXIT LIGHTS. THIS IS NO |
| | POSSIBLE. SEE NEC 760 FOR WIRING AND OTHER ADOPTED |
| | CODES SUCH AS NFPA-13 FOR REQUIRED SYSTEMS. |
| | NEC 1999 |
| | FBC 104.1.2 |
| | |
| | 7) NOTE: PLEASE BE SURE TO IDENTIFY ALL FIXTURES ON |
| | PLANS AND COORDINATE WITH THE FIXTURE LEGEND. |
| | COMPLIANCE WITH FBC 13-415.2 WILL BE VERIFIED ONCE |
| | THESE ARE DESIGNATED. |
| | PLEASE ALSO COORDINATE DESIGNATIONS. FOR EXAMPLE: |
| | EXTERIOR FIXTURES WHICH ARE NOTED AS *D* AS IDENTIFIED |
| | AS FLOOR LAMPS ON THE FIXTURE LEGEND. |
| | |
| | 8) NOTE: PLEASE SEE 13-415.1.ABCD.1.1.5 FOR CONTROLS OF |
| | EXTERIOR LIGHTING. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |