Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop B
Sequence Number 3
Notes
Date Text
2009-01-14 13:28:54BUILDING PLAN REVIEW
 PERMIT: 04121040
 ADD: 533 CLEMATIS ST
 CONT: FIVE STAR CONTRACTING GROUP
 TEL: (561)436-8508
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2001 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) PLANS WERE SUBMITTED AS A RESTAMP, BUT IN PULLING
 THE ORIGINAL ISSUED PLANS, THIS IS NOT AN EXACT RESTAMP
 BUT A REDESIGN BY THE NEW DESIGN TEAM, ADDITIONAL FEES
 ARE DUE.
  
 1E) NOTE THAT IN THE ISSUED SET OF DOCUMENTS ENERGY
 CALCULATIONS WERE SUBMITTED, NO SUCH INFORMATION WAS
 SUBMITTED UNDER THIS REVIEW. LOOK FOR MORE COMMENTS AS
 TO THE REQUIREMENTS FROM EACH OF THE TRADES.
  
 1F) PLLANS TO BE SUBMITTED FOR HISTORIC REVIEW AND
 PLANS STAMPED BEFORE ISSUANCE.
  
 2) COVERSHEET GENERAL NOTES:
  
 2A) PLEASE REVISE THE EDITION OF THE CODE WHICH THE
 PLANS WERE DESIGNED TO. THIS IS A 2004 PERMIT UNDER THE
 2001 FBC. PLEASE REVISE CODE RELATED ISSUES.
  
 2B) THE DESIGNER IS INDICATING THE BUILDING TO BE FULLY
 SPRINKLERED INCLUDING THIS SPACE BUT NO FIRE SPRINKLER
 PLANS ARE INCLUDED WITHIN THIS PERMIT PACKAGE. 2001 FBC
 104.3.1.1(5) FIRE SPRINKLERS.
  
 2C) THE COVER SHEET INDICATES THAT INTERIOR DESIGN
 DRAWINGS ARE NOT REQUIRED, THE ONLY INFORMATION
 PROVIDED IS MINIMUM INTERIOR FINISH CLASSIFICATION
 TABLE 803.3. SECTION 803.3.1 THE MINIMUM FLAMESPREAD
 CLASSIFICATION OF INTERIOR FINISH OTHER THAN FLOOR
 FINISH AND FLOOR COVERINGS SHALL BE BASED ON THE USE OR
 OCCUPANCY AS SET FORTH IN TABLE 803.3. NO INFORMATION
 WAS SUPPLIED UNDER THIS REVIEW FOR FLOOR, WALL, TRIM
 NOR CEILINGS.
  
 2D) OCCUPANCY IS INDICATED AS 170 SEATS, OR IS THAT TO
 BE THE TOTAL OCCUPANT LOAD?
  
 3) SHEET 1.0A
  
 3A) IT APPEARS THAT THE COOLER DOOR HAS BEEN CHANGED TO
 A OUTSWING DOOR COVERING MORE THAN ONE HALF OF THE
 REQUIRED EGRESS 2001 FBC 1012.1.4.
  
 3B) PLEASE REVIEW 11-5.1 FIVE PER CENT OF SEATING ARE
 TO BE ACCESSIBLE SEATS PLANS INDICATE 170 SEATS OR 9
 ACCESSIBLE SEATS, PLEASE RECOUNT SEATING IT APPEARS
 THAT THERE ARE 146 SEATS REQUIRING 8 ACCESSABLE SEATS.
  
 3C) PLEASE INDICATE THE ACCESIBLE ROUTE FOR THE
 ACCESIBLE SEATING AREAS , THE MINIMUM CLEAR WIDTH OF AN
 ACCESSIBLE ROUTE SHALL BE 36". 11-4.3.3.
  
 3D) CONSTRUCTION NOTE# 5 INDICATES NEW FIXED STOREFRONT
 WITH PRECAST LINTELS. THE PERMITED SET OF PLANS DID NOT
 MENTION ANY WORK ON THE EXTERIOR OF THE BUILDING.
 PLEASE PROVIDE INFORMATION AS TO WHERE THE NEW OPENINGS
 AND LINTELS WILL BE INSTALLED. COMPONENTS AND CLADDING,
 1606.2.5, PROTECTION OF OPENINGS LARGE MISSILE IMPACT
 GLAZING OR STORM PANELS 1606.1.4.
  
 3E) FL BLD CODE 1609.1.4: & RULE 9B-72, COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 LINTELS
 STOREFRONT- WINDOWS AND DOORS
  
 3F) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 3G) SINCE SHEET 1.0A NOTE 5 DOES INDICATE NEW
 STOREFRONT PLEASE INDICATE WHERE THE FRONT PROPERTY
 LINE IS LOCATED, SECTION 3203.
  
 4) PLANS FAIL TO INDICATE OCCUPANCY SEPERATION BETWEEN
 THE A2 OCCUPANCY AND THAT ABOVE. PLEASE PROVIDE
 WHATTYPE OF OCCUPANCY IS LOCATED ON THE SECOND FLOOR.
 TABLE 704.1 A2 ASSEMBLY 2HR.
 PLEASE PROVIDE DETAILS.
  
 5) HVAC PLAN INDICATES NEW WORK THROUGH THE HORIZONTAL
 FLOOR/ CEILING ASSEMBLY PLEASE INDICATE COMPLIANCE WITH
 705.6 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  