| 2009-01-14 13:28:54 | BUILDING PLAN REVIEW |
| | PERMIT: 04121040 |
| | ADD: 533 CLEMATIS ST |
| | CONT: FIVE STAR CONTRACTING GROUP |
| | TEL: (561)436-8508 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | W/ * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2001 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| | TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| | 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1D) PLANS WERE SUBMITTED AS A RESTAMP, BUT IN PULLING |
| | THE ORIGINAL ISSUED PLANS, THIS IS NOT AN EXACT RESTAMP |
| | BUT A REDESIGN BY THE NEW DESIGN TEAM, ADDITIONAL FEES |
| | ARE DUE. |
| | |
| | 1E) NOTE THAT IN THE ISSUED SET OF DOCUMENTS ENERGY |
| | CALCULATIONS WERE SUBMITTED, NO SUCH INFORMATION WAS |
| | SUBMITTED UNDER THIS REVIEW. LOOK FOR MORE COMMENTS AS |
| | TO THE REQUIREMENTS FROM EACH OF THE TRADES. |
| | |
| | 1F) PLLANS TO BE SUBMITTED FOR HISTORIC REVIEW AND |
| | PLANS STAMPED BEFORE ISSUANCE. |
| | |
| | 2) COVERSHEET GENERAL NOTES: |
| | |
| | 2A) PLEASE REVISE THE EDITION OF THE CODE WHICH THE |
| | PLANS WERE DESIGNED TO. THIS IS A 2004 PERMIT UNDER THE |
| | 2001 FBC. PLEASE REVISE CODE RELATED ISSUES. |
| | |
| | 2B) THE DESIGNER IS INDICATING THE BUILDING TO BE FULLY |
| | SPRINKLERED INCLUDING THIS SPACE BUT NO FIRE SPRINKLER |
| | PLANS ARE INCLUDED WITHIN THIS PERMIT PACKAGE. 2001 FBC |
| | 104.3.1.1(5) FIRE SPRINKLERS. |
| | |
| | 2C) THE COVER SHEET INDICATES THAT INTERIOR DESIGN |
| | DRAWINGS ARE NOT REQUIRED, THE ONLY INFORMATION |
| | PROVIDED IS MINIMUM INTERIOR FINISH CLASSIFICATION |
| | TABLE 803.3. SECTION 803.3.1 THE MINIMUM FLAMESPREAD |
| | CLASSIFICATION OF INTERIOR FINISH OTHER THAN FLOOR |
| | FINISH AND FLOOR COVERINGS SHALL BE BASED ON THE USE OR |
| | OCCUPANCY AS SET FORTH IN TABLE 803.3. NO INFORMATION |
| | WAS SUPPLIED UNDER THIS REVIEW FOR FLOOR, WALL, TRIM |
| | NOR CEILINGS. |
| | |
| | 2D) OCCUPANCY IS INDICATED AS 170 SEATS, OR IS THAT TO |
| | BE THE TOTAL OCCUPANT LOAD? |
| | |
| | 3) SHEET 1.0A |
| | |
| | 3A) IT APPEARS THAT THE COOLER DOOR HAS BEEN CHANGED TO |
| | A OUTSWING DOOR COVERING MORE THAN ONE HALF OF THE |
| | REQUIRED EGRESS 2001 FBC 1012.1.4. |
| | |
| | 3B) PLEASE REVIEW 11-5.1 FIVE PER CENT OF SEATING ARE |
| | TO BE ACCESSIBLE SEATS PLANS INDICATE 170 SEATS OR 9 |
| | ACCESSIBLE SEATS, PLEASE RECOUNT SEATING IT APPEARS |
| | THAT THERE ARE 146 SEATS REQUIRING 8 ACCESSABLE SEATS. |
| | |
| | 3C) PLEASE INDICATE THE ACCESIBLE ROUTE FOR THE |
| | ACCESIBLE SEATING AREAS , THE MINIMUM CLEAR WIDTH OF AN |
| | ACCESSIBLE ROUTE SHALL BE 36". 11-4.3.3. |
| | |
| | 3D) CONSTRUCTION NOTE# 5 INDICATES NEW FIXED STOREFRONT |
| | WITH PRECAST LINTELS. THE PERMITED SET OF PLANS DID NOT |
| | MENTION ANY WORK ON THE EXTERIOR OF THE BUILDING. |
| | PLEASE PROVIDE INFORMATION AS TO WHERE THE NEW OPENINGS |
| | AND LINTELS WILL BE INSTALLED. COMPONENTS AND CLADDING, |
| | 1606.2.5, PROTECTION OF OPENINGS LARGE MISSILE IMPACT |
| | GLAZING OR STORM PANELS 1606.1.4. |
| | |
| | 3E) FL BLD CODE 1609.1.4: & RULE 9B-72, COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS |
| | ,MISSING REPORTS ARE AS FOLLOWS: |
| | LINTELS |
| | STOREFRONT- WINDOWS AND DOORS |
| | |
| | 3F) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. |
| | |
| | 3G) SINCE SHEET 1.0A NOTE 5 DOES INDICATE NEW |
| | STOREFRONT PLEASE INDICATE WHERE THE FRONT PROPERTY |
| | LINE IS LOCATED, SECTION 3203. |
| | |
| | 4) PLANS FAIL TO INDICATE OCCUPANCY SEPERATION BETWEEN |
| | THE A2 OCCUPANCY AND THAT ABOVE. PLEASE PROVIDE |
| | WHATTYPE OF OCCUPANCY IS LOCATED ON THE SECOND FLOOR. |
| | TABLE 704.1 A2 ASSEMBLY 2HR. |
| | PLEASE PROVIDE DETAILS. |
| | |
| | 5) HVAC PLAN INDICATES NEW WORK THROUGH THE HORIZONTAL |
| | FLOOR/ CEILING ASSEMBLY PLEASE INDICATE COMPLIANCE WITH |
| | 705.6 PENETRATIONS OF HORIZONTAL ASSEMBLIES. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |