| Plan Review Notes For Permit 04121040 |
| Permit Number |
04121040 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | | | | 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 - | | | SHEETS REQUESTED ON 3-09-5 WERE FAXED | | | OVER ON 3-14-5 - CALLED CONTRACTOR | | | ADVISING NEW APPLIANCES WERE SHOWN AND | | | SHEET WERE REQUIRED FOR THOSE AND THAT A | | | DIFFERENT GAS APPLIANCE LAYOUT WAS FAXED | | | WITH SHEETS. NEW SHEETS DO NOT CORRELATE | | | WITH BTU'S LISTED ON PLANS AND SOME | | | SHEETS SHOW APPLIANCES NOT SHOWN ON THE | | | GAS RISER DIAGRAM. ED BRAHMAN INDICATED | | | ON 3-14-5 HE WILL GET BACK TO ME ON THIS | | | BUT DID NOT. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|