2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 -
 SHEETS REQUESTED ON 3-09-5 WERE FAXED
 OVER ON 3-14-5 - CALLED CONTRACTOR
 ADVISING NEW APPLIANCES WERE SHOWN AND
 SHEET WERE REQUIRED FOR THOSE AND THAT A
 DIFFERENT GAS APPLIANCE LAYOUT WAS FAXED
 WITH SHEETS. NEW SHEETS DO NOT CORRELATE
 WITH BTU'S LISTED ON PLANS AND SOME
 SHEETS SHOW APPLIANCES NOT SHOWN ON THE
 GAS RISER DIAGRAM. ED BRAHMAN INDICATED
 ON 3-14-5 HE WILL GET BACK TO ME ON THIS
 BUT DID NOT.
  
  