| Notes |
| Date |
Text |
| 2005-03-08 00:00:00 | PASS PRIVISO | | | 1) HOOD EXHAUST MUST TERMINATE 40 | | | IN.ABOVE ROOF NFPA 96 FIGURE A.4.2(D) | | | 2) SUPPLY HANGING DETAL FOR HOOD BEFOR | | | ROUGH INSPECTION | | | 3) YOU NEED HORN & STROBE FOR FAN | | | SHUTDOWN NOT A KEY SWITCH.THE MINIMUM | | | SOUND PRESSURE SHALL BE 60DBA MAXIMUM | | | SOUND PRESSURE SHALL BE 130DBA.STROBE | | | MUST BE SEEN FROM ANY PART OF THE | | | RESTAURANT. | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|