2005-03-08 00:00:00PASS PRIVISO
 1) HOOD EXHAUST MUST TERMINATE 40
 IN.ABOVE ROOF NFPA 96 FIGURE A.4.2(D)
 2) SUPPLY HANGING DETAL FOR HOOD BEFOR
 ROUGH INSPECTION
 3) YOU NEED HORN & STROBE FOR FAN
 SHUTDOWN NOT A KEY SWITCH.THE MINIMUM
 SOUND PRESSURE SHALL BE 60DBA MAXIMUM
 SOUND PRESSURE SHALL BE 130DBA.STROBE
 MUST BE SEEN FROM ANY PART OF THE
 RESTAURANT.
 PLAN REVIEW BY HAROLD MOSER