| Date |
Text |
| 2005-02-23 00:00:00 | REDLINED NOTES: | | | | | | | | | EQUIPMENT GROUNDING CONDUCTOR STILL | | | SHOWN FROM GUTTER TO METER AND METER TO | | | FIRST MEANS OF DISCONNECT. | | | THIS SHALL NOT BE INSTALLED. | | | 250.6,250.24 | | | | | | BAR AREA RECEPTS TO BE GFI 210.8 |
|