Plan Review Notes
Plan Review Notes For Permit 04121040
Permit Number 04121040
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-23 00:00:00REDLINED NOTES:
  
  
 EQUIPMENT GROUNDING CONDUCTOR STILL
 SHOWN FROM GUTTER TO METER AND METER TO
 FIRST MEANS OF DISCONNECT.
 THIS SHALL NOT BE INSTALLED.
 250.6,250.24
  
 BAR AREA RECEPTS TO BE GFI 210.8