2005-01-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 PER WASTE ORD. #2938-96. (561) 837-4074
 2) SHT A2.0 EQUIPMENT SCHEDULE #3 NOT
 FOUND ON THE FLOOR PLAN. PLEASE CLARIFY
 SECTION 104.2.1.
 3) SHT A2.0 FIRST FLOOR PLAN. RED LINE
 MARKINGS FROM THE FDBR HOTEL AND
 RESTURANT DIV. INDICATES THAT 2 NEW HAND
 SINKS ARE REQUIRED AND ONE OTHER HAND
 SINK SHALL BE DELETED. PLEASE REVISE
 SHT
 A2.0 SHOWING THESE REQUIREMENTS.
 RESUBMIT STAMPED SHEET A2.0 WITH NEW
 SHT
 A2.0 AND INDICATE ON SHEET FOR DBPR
 STAMP ONLY.
 4) RPZ BACKFLOW IS REQUIRED ON THE WATER
 SERVICE. SECTION 608.13.2.
 5) SHTS P2.1, P5.1, & P5.2 DO NOT SHOW
 NEW HAND SINKS REQUIRED BY DBPR, NOR DO
 THEY SHOW THE HAND SINK DELETED BY DBPR.
 PLEASE REVISE AS REQUIRED. SECTION
 104.2.1.
 6) SHT P5.1 GAS RISER DIAGRAM. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE REQUIRED GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 D. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 7) SHT P6.2 WATER FILTER FOR ICE MAKER
 SHALL COMPLY WITH NSF-42. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEET SHOWING
 COMPLIANCE.
  