| Plan Review Notes For Permit 04121040 |
| Permit Number |
04121040 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-21 00:00:00 | 1. PLEASE PROVIDE DIMENSIONS FOR THE | | | LOOS CHAIRS LOCATED AT THE TABLES. | | | SOME OF THE LOOSE CHAIRS APPEAR TO | | | BE LOCATED TOO CLOSE TOGETHER. | | | | | | 2. ALL WALK-IN COOLERS AND FREEZERS | | | ARE TO BE FIRE SPRINKLER PROTECTED. | | | | | | 3. DEMOLITION, RENOVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 4. PANIC HARDWARE REQUIRED ON ALL | | | EXIT DOORS SUBJECT TO AN OCCUPANCY | | | OF 100 OR MORE PERSONS. | | | | | | 5. HOOD EXHAUST DUCT TERMINATION | | | POINT APPEARS TO BE DIRECTLY | | | ADJACENT TO THE REAR EXIT DOOR. | | | | | | 6. PLEASE PROVIDE PRODUCT APPROVALS | | | FOR THE HOOD EXHAUST DUCT WRAP. | | | | | | 7. SEPARATE PLANS AND PERMITS | | | REQUIRED FOR ANY FIRE SPRINKLER | | | REMODEL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 | | | |
|