2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121040
 ADD: 533 CLEMATIS STREET
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)705-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A2.0 FIRE RATING NOTE
 INDICATES
 THAT THE COLUMNS WILL BE FIRE PROTECTED
 WITH SPRAY APPLIED FIRE RESISTANT
 MATERIALS ONTO THE STEEL COLUMN. PLANS
 INDICATE USING U.L. X827 FOR THE FIRE
 RATING BUT THE SIZE OF THE COLUMN IS NOT
  
 STATED NOR THE MINIMUM THICKNESS OF
 INSULATION OR TYPE OF SPRAY INSULATION.
  
 3) SHEET M6.1 CONDENSING UNIT DETAILS:
 A) CORRECT CODE AND REFENCE NUMBER,
 2001 FL BLDG CODE, 1511.7.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026