| Date |
Text |
| 2004-12-28 00:00:00 | **************** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| | FAC 61G15-23.002 FOR MISSING LICENSE |
| | INFORMATION FOR ARCHITECTS AND |
| | ENGINEERINGFIRM PER FS 481.219, |
| | 471.023. |
| | THIS INFORMATION IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2)NOTE: PLANS WHICH CONTAIN THE TITLE |
| | BLOCK FOR ENGINEER RESPONSIBLE FOR |
| | PLANS/DESIGN, MUST SIGN, DATE AND SEAL |
| | PLANS. FS 471.025 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 4)NOTE: PLEASE SEE 220.31B FOR LOAD |
| | CALCUALTIONS. |
| | |
| | |
| | **PLEASE NOTE*** |
| | PLANS MENTIONS KNOB AND TUBE WIRING |
| | PRESENT. |
| | UPON SERVICE CHANGE, IF KNOB AND TUBE IS |
| | STILL PRESENT THEN, THE CONNECTION OF |
| | THESE CIRCUITS WILL NOT BE PERMITTED. |
| | RE-WIRE MUST BE PERMITTED AND COMPLETE |
| | BEFORE CALLING IN FINALS FOR PERMITS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |