| Plan Review Notes For Permit 04121009 |
| Permit Number |
04121009 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-28 00:00:00 | ******** UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAINS TO | | | PANELS. | | | 250.110,250.24, SIZE PER 250.122 | | | | | | 2)NOTE: PLEASE SEE A SECOND WATER | | | HEATER | | | IS MENTIONED ON PANEL SCHEDULE FOR | | | MASTER BEDRM, YET THIS SECOND UNIT | | | COULD | | | NOT BE LOCATED ON PLANS.? | | | | | | 3)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY | | | NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE 250.66 FOR SIZING OF | | | GROUNDING ELECTRODE CONDUCTOR. (#2 MIN) | | | | | | PLEASE VERIFY OCP FOR OVEN. 50A FOR 6.5 | | | KW? THIS IS ONLY A NOTE: | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|