Plan Review Notes
Plan Review Notes For Permit 04121009
Permit Number 04121009
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-28 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS.
 250.110,250.24, SIZE PER 250.122
  
 2)NOTE: PLEASE SEE A SECOND WATER
 HEATER
 IS MENTIONED ON PANEL SCHEDULE FOR
 MASTER BEDRM, YET THIS SECOND UNIT
 COULD
 NOT BE LOCATED ON PLANS.?
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY
 NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 215.5
  
 4)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GROUNDING ELECTRODE CONDUCTOR. (#2 MIN)
  
 PLEASE VERIFY OCP FOR OVEN. 50A FOR 6.5
 KW? THIS IS ONLY A NOTE:
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717