Plan Review Notes
Plan Review Notes For Permit 04120966
Permit Number 04120966
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SEE BUILDING REVIEW CONCERNING THE
 ADDRESS.
 2) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) FLUSH CONTROLS 11-4.16.5
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4
 E) FAUCETS 11-4.19.6
 F) THE WATER CLOSET SHALL BE 18" FROM
 THE CENTERLINE OF THE FIXTURE TO THE
 WALL. FIG. 28
 G) THE LAV SHALL CENTER ON THE 30"
 MEASURMENT OF THE 30"X48" CLEAR FLOOR
 SPACE AND SHALL BE MIN. OF 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE.
 3) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
 4) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS
 SHOWN ON THE LAVS ARE NOT APPROVED.
 DELETE FROM ISOMETRIC. SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]