| Plan Review Notes For Permit 04120966 |
| Permit Number |
04120966 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 KEYNOTE #7 O.A. | | | LOCATED ABOVE THE CEILING AS SHOWN FOR | | | FUTURE USE BY ADJACENT TENANT.PER 2001 | | | FBC 704.3..1 WHEN ENCLOSED SPACES ARE | | | PROVIDED FOR SEPARATE TENANTS, SPACES | | | SHALL BE SEPARATED BY A 1 HR FIRE | | | RESISTANCE.PLEASE PROVIDE FIRE DAMPERS | | | AS REQUIRED PER 2001 FBC(M)607.1.2 AND | | | IDENTIFY LOCATIONS ON THE PLANS IN | | | ACCORDANCE WITH 2001 FBC(M)607.6. | | | | | | 2.PLAN SHEET M-2 & P-1 INDICATE | | | AUXILIARY DRAIN LINE TERMINATING OUTSIDE | | | THE BUILDING.PER 2001 FBC(M)307.2.3, | | | AUXILIARY DRAIN LINE IS TO TERMINATE AT | | | A CONSPICUOUS POINT TO SERVE AS AN ALARM | | | THAT THE PRIMARY DRAIN IS RETSTRICTED. | | | PLEASE REVISE ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|