2005-01-19 00:00:00DENIED:
 1.PLAN SHEET M-1 KEYNOTE #7 O.A.
 LOCATED ABOVE THE CEILING AS SHOWN FOR
 FUTURE USE BY ADJACENT TENANT.PER 2001
 FBC 704.3..1 WHEN ENCLOSED SPACES ARE
 PROVIDED FOR SEPARATE TENANTS, SPACES
 SHALL BE SEPARATED BY A 1 HR FIRE
 RESISTANCE.PLEASE PROVIDE FIRE DAMPERS
 AS REQUIRED PER 2001 FBC(M)607.1.2 AND
 IDENTIFY LOCATIONS ON THE PLANS IN
 ACCORDANCE WITH 2001 FBC(M)607.6.
  
 2.PLAN SHEET M-2 & P-1 INDICATE
 AUXILIARY DRAIN LINE TERMINATING OUTSIDE
 THE BUILDING.PER 2001 FBC(M)307.2.3,
 AUXILIARY DRAIN LINE IS TO TERMINATE AT
 A CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RETSTRICTED.
 PLEASE REVISE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.