2004-12-29 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE RISER SHOWS
 MAIN/METER THE SAME AS UNITSC & D.
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE NOTE TO SERVICE LOAD
 MENTIONS THIS IS AN ESTIMATED LAOD OF
 20WP/SQ FT. PLEASE SEE THIS IS SHOWN
 FOR
 GEN LT LOADS AND EST FOR LOADS NOT
 KNOWN.
 PLEASE SEE SOME UNIT ARE KNOW AT THIS
 TIME AND INCLUDING ONE AS A REST. FIT
 UP.
 KNOWN LOADS MUST BE FIGURED INTO
 SERVICE
 LOAD CALCULATIONS.220.3B
  
 3)NOTE: PLEASE PROVIDE A NOTE ON RISER
 FOR A "FLOATING NEUTRAL REQUIRED" IN
 TENANT METERS. PLEASE SEE 250.6,
 250.24.
  
 4)NOTE: PLEASE SEE PLANS REFERENCE 5707
 S DIXIE, YET SYSTEM SHOWS 5707? PLEASE
 SEE BLDG REVIEW COMMENTS AND POSSIBLE
 ADDRESS CORRELATION.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  