| Plan Review Notes For Permit 04120966 |
| Permit Number |
04120966 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-29 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE SEE RISER SHOWS | | | MAIN/METER THE SAME AS UNITSC & D. | | | PLEASE ADJUST. | | | | | | 2)NOTE: PLEASE SEE NOTE TO SERVICE LOAD | | | MENTIONS THIS IS AN ESTIMATED LAOD OF | | | 20WP/SQ FT. PLEASE SEE THIS IS SHOWN | | | FOR | | | GEN LT LOADS AND EST FOR LOADS NOT | | | KNOWN. | | | PLEASE SEE SOME UNIT ARE KNOW AT THIS | | | TIME AND INCLUDING ONE AS A REST. FIT | | | UP. | | | KNOWN LOADS MUST BE FIGURED INTO | | | SERVICE | | | LOAD CALCULATIONS.220.3B | | | | | | 3)NOTE: PLEASE PROVIDE A NOTE ON RISER | | | FOR A "FLOATING NEUTRAL REQUIRED" IN | | | TENANT METERS. PLEASE SEE 250.6, | | | 250.24. | | | | | | 4)NOTE: PLEASE SEE PLANS REFERENCE 5707 | | | S DIXIE, YET SYSTEM SHOWS 5707? PLEASE | | | SEE BLDG REVIEW COMMENTS AND POSSIBLE | | | ADDRESS CORRELATION. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|