Plan Review Notes
Plan Review Notes For Permit 04120965
Permit Number 04120965
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SEE BUILDING REVIEW CONCERNING THE
 ADDRESS.
 2) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) FLUSH CONTROLS 11-4.16.5
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4
 E) FAUCETS 11-4.19.6
 F) THE WATER CLOSET SHALL BE 18" FROM
 THE CENTERLINE OF THE FIXTURE TO THE
 WALL. FIG. 28
 G) THE LAV SHALL CENTER ON THE 30"
 MEASURMENT OF THE 30"X48" CLEAR FLOOR
 SPACE AND SHALL BE MIN. OF 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE.
 3) MORE INFORMATION IS REQUIRED ON THE
 OCCUPANCY. INDICATE TYPE OF BUSINESS
 WILL BE IN THE SPACE. - MORE COMMENTS
 MAY FOLLOW AFTER COMMENT RESPONSE IS
 RECIEVED. SECTION 104.2.1.
 4) SHT P-1 THREE COMPARTMENT SINK IN THE
 FOOD PREP AREA SHALL DRAIN INDIRECTLY
 INTO AN APPROVED INDIRECT WASTE
 RECEPTICAL PER SECTION 802.1.1 & 802.3.
 5) GREASE INTECEPTOR MAY BE REQUIRED.
 CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE @ (561) 837-4074. WASTE ORD.
 NUMBER 2938-96.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]