Plan Review Notes
Plan Review Notes For Permit 04120965
Permit Number 04120965
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00DENIED:
 1. PLAN SHEET M-1 & P-1, AUXILIARY DRAIN
 LINE IS SHOWN TERMINATING OUTSIDE OF THE
 BUILDING AREA.PER 2001 FBC(M)307.2.3,
 AUXILIARY DRAIN LINE IS TO TERMINATE AT
 A CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
 PLEASE REVISE ACCORDINGLY.
  
 2. PLAN M-1 KEYNOTE #3 INDICATES O.A.
 STUBBED FROM THE ADJACENT TENANT.
 PLEASE CLARIFY THE FOLLOWING:
 - FIRE DAMPER BETWEEN THE TENANT
 SEPARATION.
 - INDICATE WHERE THE O.A. INTAKE IS
 LOCATED.
 - O.A. CAN NOT BE TAKEN FROM THE
 ADJACENT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  