| Plan Review Notes For Permit 04120965 |
| Permit Number |
04120965 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | DENIED: | | | 1. PLAN SHEET M-1 & P-1, AUXILIARY DRAIN | | | LINE IS SHOWN TERMINATING OUTSIDE OF THE | | | BUILDING AREA.PER 2001 FBC(M)307.2.3, | | | AUXILIARY DRAIN LINE IS TO TERMINATE AT | | | A CONSPICUOUS POINT TO SERVE AS AN ALARM | | | THAT THE PRIMARY DRAIN IS RESTRICTED. | | | PLEASE REVISE ACCORDINGLY. | | | | | | 2. PLAN M-1 KEYNOTE #3 INDICATES O.A. | | | STUBBED FROM THE ADJACENT TENANT. | | | PLEASE CLARIFY THE FOLLOWING: | | | - FIRE DAMPER BETWEEN THE TENANT | | | SEPARATION. | | | - INDICATE WHERE THE O.A. INTAKE IS | | | LOCATED. | | | - O.A. CAN NOT BE TAKEN FROM THE | | | ADJACENT SPACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|