| 2005-01-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04120965 |
| | ADD: 5705 S DIXIE BAY E |
| | CONT: SUNDOWN |
| | TEL: (561)743-4420 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)CONTACT JOHN HIGGINS @ (561)822-1239 |
| | TO CORRECT ADDRESS. CITY INDICATES 5705 |
| | S DIXIE NOT 5707. |
| | 1A) USPS POSTAL STANDARD DOESN'T ALLOW |
| | BAYS TO BE IDENTIFIED BY ALPHABETICAL |
| | TERMS (BAY-A). |
| | |
| | 2) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 4) 1511.7 ROOF MOUNTED MECHANICAL UNIT S |
| | SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUP PORTS THAT |
| | ARE EXPOSED TO WIND SHALL BE DESIGNED |
| | AND INSTALLED TO RESIST THE WIND |
| | PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | |
| | 5)FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| | PROVIDE ENERGY CALS/ W MANUAL "J" |
| | |
| | 6) 11-5.2 COUNTERS AND BARS |
| | WHERE FOOD OR DRINK IS SERVED @ COUNTERS |
| | EXCEEDING 34" IN HEIGHT FOR CONSUMPTION |
| | BY CUSTOMERS SEATED ON STOOLS OR STAND- |
| | ING AT THE COUNTER, A PORTION OF THE |
| | MAIN COUNTER WHICH IS 60" IN LENGTH MIN- |
| | IMUM SHALL BE PROVIDED IN COMPLIANCE |
| | WITH 11-4.32 OR SERVICE SHALL BE AVAIL- |
| | ABLE AT ACCESSIBLE TABLES WITHIN THE |
| | SAME AREA. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |