Plan Review Notes For Permit 04120964
Permit Number 04120964
Review Stop P
Sequence Number 2
Notes
Date Text
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND BUSINESS DIVISION FOR REVIEW PRIOR
 TO RESUBMITTING TO WPB CONST. SERVICES
 FOR RESUBMITTING. PLANS SHALL BE STAMPED
 BY DBPR AND WORKSHEETS ATTACHED.
 2) GREASE INTECEPTOR MAY BE REQUIRED.
 CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR DETERMINATION. WASTE ORD.
 2938-96 (561) 837-4074. WORK SHEET FROM
 MR. COMPO SHALL ACCOMPANY PLANS WHEN
 RESUBMITTING.
 3) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 CHOW COMPLIANCE.
 A) FLUSH CONTROLS 11-4.16.5
 B) FAUCETS 11-4.19.6
 4) SHT P-1 SANITARY RISER DIAGRAM AND
 PLUMBING FLOOR PLAN, 3 COMPARTMENT SINK
 SHALL DRAIN TO AN INDIRECT WASTE (FLOOR
 SINK) PER SECTION 802.1.1.
 5) INDICATE IF SEATING WILL BE AVAILABLE
 OR WILL THIS BE TAKE OUT ONLY.
 6) AN RPZ BACKFLOW WILL BE REQUIRED ON
 THE WATER SERVICE. SECTION 608.13.2.
 7) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2.
 8) TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO FOOD SERVING AREAS OR DINING AREAS.
 SECTION 423.16.10.1 BUILDING CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]