| 2005-02-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PLANS SHALL BE ROUTED TO DBPR HOTEL |
| | AND BUSINESS DIVISION FOR REVIEW PRIOR |
| | TO RESUBMITTING TO WPB CONST. SERVICES |
| | FOR RESUBMITTING. PLANS SHALL BE STAMPED |
| | BY DBPR AND WORKSHEETS ATTACHED. |
| | 2) GREASE INTECEPTOR MAY BE REQUIRED. |
| | CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR DETERMINATION. WASTE ORD. |
| | 2938-96 (561) 837-4074. WORK SHEET FROM |
| | MR. COMPO SHALL ACCOMPANY PLANS WHEN |
| | RESUBMITTING. |
| | 3) SHT A-1 BATHROOM DETAIL. THE |
| | FOLLOWING INFORMATION IS REQUIRED TO |
| | CHOW COMPLIANCE. |
| | A) FLUSH CONTROLS 11-4.16.5 |
| | B) FAUCETS 11-4.19.6 |
| | 4) SHT P-1 SANITARY RISER DIAGRAM AND |
| | PLUMBING FLOOR PLAN, 3 COMPARTMENT SINK |
| | SHALL DRAIN TO AN INDIRECT WASTE (FLOOR |
| | SINK) PER SECTION 802.1.1. |
| | 5) INDICATE IF SEATING WILL BE AVAILABLE |
| | OR WILL THIS BE TAKE OUT ONLY. |
| | 6) AN RPZ BACKFLOW WILL BE REQUIRED ON |
| | THE WATER SERVICE. SECTION 608.13.2. |
| | 7) THERMAL EXPANSION CONTROL IS REQUIRED |
| | PER SECTION 607.3.2. |
| | 8) TOILET ROOMS SHALL NOT OPEN DIRECTLY |
| | INTO FOOD SERVING AREAS OR DINING AREAS. |
| | SECTION 423.16.10.1 BUILDING CODE. |
| | |