Date Text
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SEE BUILDING REVIEW CONCERNING THE
 ADDRESS.
 2) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) FLUSH CONTROLS 11-4.16.5
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4
 E) FAUCETS 11-4.19.6
 F) THE WATER CLOSET SHALL BE 18" FROM
 THE CENTERLINE OF THE FIXTURE TO THE
 WALL. FIG. 28
 G) THE LAV SHALL CENTER ON THE 30"
 MEASURMENT OF THE 30"X48" CLEAR FLOOR
 SPACE AND SHALL BE MIN. OF 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE.
 3) SUBMIT A SANITARY AND A WATER RISER
 DIAGRAM. SHOW ALL PIPE SIZES AND SHOW
 WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 LOCATED NEAR THE FIXTURE,
 NOT IN THE CEILING PER PDI-WH 201. AIR
 CHAMBERS ARE NOT APPROVED.
 4) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
  