| Plan Review Notes For Permit 04120962 |
| Permit Number |
04120962 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | A) FROM PREVIOUS REVIEW: | | | 2) SHT A-1 BATHROOM DETAIL. THE | | | FOLLOWING INFORMATION IS REQUIRED TO | | | SHOW COMPLIANCE WITH SECTIONS 11-4.16, | | | 11-4.19, & 11-4.22 | | | B) FLUSH CONTROLS 11-4.16.5 | | | E) FAUCETS 11-4.19.6 | | | 4) PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED. ALSO SE SECTION 410.1 - | | | SHOW THE LOCATION OF THE WATER COOLER ON | | | THE PLANS. SECTION 104.2.1. | | | ************NEW COMMENT************ | | | 1B) FUTURE SINK SHALL NOT DRAIN THROUGH | | | THE HORIZONTAL WET VENT OF THE BATHROOM | | | FIXTURES, BUT SHALL DISCHARGE DOWNSTREAM | | | OF THE FIXTURES. SECTION 909.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|