Plan Review Notes
Plan Review Notes For Permit 04120962
Permit Number 04120962
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120962
 ADD: 5705 S DIXIE HWY BAYS A&B
 CONT: SUNDOWN DEVELOPMENT
 TEL: (561)743-4420
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) CONTACT JOHN HIGGINS @ (561)822-1239
 TO CORRECT ADDRESS.CITY INDICATES 5705
 S DIXIE NOT 5707.
 1A) USPS POSTAL STANDARD DO NOT ALLOW
 BAYS TO BE IDENTIFIED BY ALPHABETICAL
 TERMS (BAY-A, BAY-B)
  
 2)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) 11-4.16.4 GRAB BARS FOR WATER CLOSET
  
 SEE FIGURE 29 MISSING THE GRAB BAR
 BEHIND THE WATER CLOSET.
  
 6) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026