Plan Review Notes
Plan Review Notes For Permit 04120950
Permit Number 04120950
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-20 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SUBMIT A DRAWING (FOOTPRINT ) OF THE
 BUILDING SHOWING THE WINDOWS & DOORS.
 THE ROOMS MUST BE LABELED TO ASSURE
 MEANS OF EGRESS. SHOW SIZES OF WINDOWS.
  
 2. THE TRACO 2100 SERIES IS NOT IMPACT.
 IF MORE THAN 25% OF THE GLASS AREA IS
 BEING REPLACED YOU MUST PROVIDE
 HURRICANE PROTECTION.
  
 3. SUBMIT 2 COPIES OF THE FLORIDA
 PRODUCT APPROVAL FOR THE
 MASONITE/PREMDOR. HIGHLIGHT THE DOORS
 YOU ARE USING.ONLY ONE COPY OF THE
 MIAMI-DADE PRODUCT APPROVAL WAS
 SUBMITTED.THE DOORS ARE NOT IMPACT
 RATED.HURRICANE PANELS WOULD BE
 REQUIRED. DO THE DOORS HAVE SIDELITES?
  
 3. SUBMIT A DESCRIPTION OF THE AREA
 WHERE PLASTER WORK IS TO BE DONE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved