| Notes |
| Date |
Text |
| 2006-06-12 00:00:00 | PLUMBING REVISION DENIED; | | | B-1 SANITARY RISER DIAGRAM, AUTOMATIC | | | CLOTHES WASHER CAN NOT BE INSTALLED AS | | | DRAWN, DOES NOT MEET CODE SEE FBC-2001 | | | SEC. 908.3. A MECHANICAL VENT WILL ONLY | | | WORK UNDER A NEGATIVE PRESSURE, VERTICAL | | | RISERS MAY CREATE A POSITIVE PRESSURE. | | | CLEANOUT SHOULD SHOULD BE INSTALLED AT | | | 48" AFF. | | | ONE SET OF DRAWINGS MARKED IN RED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|