Plan Review Notes
Plan Review Notes For Permit 04120945
Permit Number 04120945
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATEVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 2. SHT P-1 INDICATES UNITS C1 & C2, BUT
 NO PLUMBING FLOOR PLANS OR RISER
 DIAGRAMS ARE SUBMITTED. PLEASE CLARIFY.
 SECTION 104.2.1. - NO COMMENT RESPONSE.
 COMMENT NOT ADDRESSED.
 3. SHT P-3 WATER RISER DIAGRAMS. THE
 WATER HAMMER ARRESTORS ARE REQUIRED ANT
 THE WASH MACHINE HOT AND COLD WATER, AT
 THE DISHWASHER, AND AT THE REFRIG. THEY
 WILL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 604.9 AND PDI-WH 201. - WATER
 HAMMER ARRESTORS ARE STILL SHOWN IN THE
 CEILING, AND ARE NOT SHOWN AT THE WASH
 MACHINE BOX AS REQUIRED.
 4. SHT P-3 SANITARY RISER DIAGRAM. APT
 B1, 2ND BATH, THIRD FLOOR, SHOWER/TUB
 NOT VENTED. SECTION 901.2.1. - NO
 COMMENT RESPONSE. COMMENT NOT ADDRESSED.
  
 ****************NEW COMMENTS************
 1B. SURVEY SHEETS ARE NOT SIGNED, SEALED
 & DATED AS REQUIRED PER 61G15-23.002(1)
 AND FS 471.025. ALSO ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. FAC
 61G15-23.002(2)
 2B. SHTS C1.00 THRU C4.00 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 LIGALLY REGISTERED UNDER THE LAWS OF
 THIS STATE REGULATING THE PRACTICE OF
 ARCHITECTURE OR ENGINEERING, THEN HE/SHE
 SHALL AFFIX HIS/HER OFFICIAL SEAL TO
 SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. SECTION 104.2.2. - ALSO
 ALL LICENSE NUMBERS, CERT. OF
 AUTHORIZATIONS, PRINTED NAME OF DESIGN
 PROFESSIONAL ECT REQUIRED BY FAC & FS.
 3B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553,80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]