2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120945
 ADD: 2018 PONCE DE LEON
 CONT: TAYCON
 TEL: (561762-0606
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 PRODUCT APPROVALS
 1) THE FL COVERSHEET FOR PGT FIXED
 WINDOWS WAS SUBMITTED BUT NOT THE NOA.
  
 2) THE SAAME HOLDS TRUE WITH THE PGT
 MULLIONS ONLY THE COVERSHEETWHILE THE
 REPORT INDICATES VAARIOUS NOA'S ARE
 COVERED WITHIN THIS REPORT.
  
 3) UNDER THE GARAGE DOOR REPORT
 HIGHLIGHT OR INDICATE WHICH DOOR OR
 SERIES YOU ENTENDTO USE?
  
 4) STEEL ROOF PANELS ALSO INDICATE WHICH
 SYSTEM INSULATED OR NOT? IF USING THE
 NONINSULATED SYSTEM THE SYSTEM
 LIMITATION OF A -60 MAXIMUM DESIGN
 PRESSURE. YOUR ENGINEER CALCULATED AN
 END ZONE PRESSURE OF -54.1 BUT USING THE
 TRIBUTARY AREA OF 55 SQ FT. HE NOTES THE
 END ZONE IS 3'. 3'X3'=9 SQ FT. AGAIN THE
  
 TABLES IN 1606.2B INDICATE A -68.1 WHICH
 WILL REQUIRE ENHANCED FASTENING BY YOUR
 ENGINEER ONLY FOR ZONE 3.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  