1 |
|
| Notes |
| Date |
Text |
| 2005-01-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) ARCHITECT SHALL SHOW THE CERTIFICATE | | | OF AUTHROIZATION ON THE TITLE BLOCK. | | | SEE | | | 61G1-16.004(2) & FS 481.219. | | | 2) SHT P-1 INDICATES UNITS C1 & C2, BUT | | | NO PLUMBING FLOOR PLANS OR RISER | | | DIAGRAMS ARE SUBMITTED. PLEAS CLARIFY. | | | 3) SHT P-3 WATER RISER DIAGRAMS. THE | | | WATER HAMMER ARRESTORS ARE REQUIRED AT | | | THE WASH MACHINE HOT AND COLD WATER, AT | | | THE DISHWASHER, AND AT THE | | | REFRIDGERATOR. THEY WILL BE LOCATED | | | NEAR | | | THE FIXTURE IN AN EFFECTIVE RANGE, NOT | | | IN THE CEILING. SECTION 604.9, AND | | | PDI-WH 201. | | | 4) SHT P-3 SANITARY RISER DIAGRAM. APT | | | B1, 2ND BATH, THIRD FLOOR, SHWR/TUB NOT | | | VENTED. SECTION 901.2.1. | | | 5) SHT P-4 FIXTURE SCHEDULE, W/M SHOWS | | | A | | | 1-1/2" TRAP. MINIMUM 2" TRAP REQUIRED. | | | TABLE 709.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|