| 2004-12-28 00:00:00 | ********* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE IT DOES NOT APPEAR |
| | THIS PERMIT MAY PULLED AS OWNER BUILDER. |
| | PAPA INDICATES THIS IS NOT PRIMARY |
| | RESIDENCE FOR HOMESTEAD. PLEASE SEE |
| | ATTACHED SHEETS PRINTED FROM PAPA |
| | SHOWING MULTIPLE HOUSES/UNITS OWNED BY |
| | THE SAME PERSON W/OUT HOMESTEAD. |
| | PLEASE SEE OWNER/ BUILDER DISCLOSURE FS |
| | 489. THIS MUST BE PRIMARY RESIDENCE |
| | ETC. |
| | |
| | 2)NOTE: PLANS DO NOT INDICATE LOCATION |
| | OF SERVICE? |
| | PLEASE SEE 250.32,225.31 ETC . REVIEW |
| | FOR THIS PART OF CODE COMPLIANCE MAY NOT |
| | BE DONE AT THIS TIME. |
| | |
| | 3)NOTE: PLEASE SEE RISER MENTIONS A NEW |
| | METER/MAIN COMBO, YET RISER INDICATES A |
| | NEW 250A MAIN DISC? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE RISER IS MISSING |
| | SEC'S PER 310.15B6,310.16 |
| | |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| | GROUNDING ELECTRODE SYSTEM. |
| | |
| | 7)NOTE: PLEASE SEE THERE ARE MANY ITEMS |
| | INDICATED ON PANEL SCHEDULE, YET THESE |
| | DO NOT APPEAR ON PLANS?? |
| | PLEASE COMPLETE PLANS.215.5 |
| | |
| | 8)NOTE: PLEASE SEE 410.8 FOR LT SHOWN IN |
| | CLOSET. MIN CLEARENCE REQUIRED. |
| | |
| | 9)NOTE: PLEASE SEE SD REQUIRED OUTSIDE |
| | BEDRM IN LIVING RM AREA. NFPA-72 |
| | 8-1.4.1.6.2 |
| | |
| | 10)NOTE: PLEASE SEE ZONING COMMENTS FOR |
| | WHEATHER OR NOT THIS NEW APT UNIT IS |
| | PERMITTED. |
| | THIS WOULD AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |