Plan Review Notes
Plan Review Notes For Permit 04120942
Permit Number 04120942
Review Stop P
Sequence Number 4
Notes
Date Text
2006-05-12 00:00:00******DENIED******
 REFERENCE: FBC-2001 PLUMBING, AND CITY
 OF WEST PALM BEACH AMENDMENTS TO THE
 FBC-2001, CHAPTER 1, ADMINISTRATION:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR THE PLUMBING
 REVISION:
  
 1. PER FBC-2001 PLBG. SECTION 901.2.1
 VENTING REQUIRED, . THE SHOWER AND TUB
 IN THE MASTER BATH ROOM #303 AND THE
 SHOWER/TUB IN BATH-2 ROOM #306 ARE NOT
 VENTED. PLEASE CORRECT.
 2. PER CITY OF W.P.B. AMENDMENTS,
 SECTION 104.2.1 REQUIREMENTS. THE
 ISOMETRIC DRAWING ON SHEET P-3 DOES NOT
 REFLECT THE FLOOR PLAN OF SHEET P-2. THE
 ISOMETRIC ON SHEET P-3 INDICATES A 3"
 VTR STRAIGHT UP THROUGH THE MASTER BATH
 FLOOR, WHERE SHEET P-2 INDICATES THE 3"
 VENT IN THE WALL BY THE W/C, PLEASE
 CORRELATE THE ISOMETRIC ON P-3 WITH THE
 FLOOR PLAN ON P-2.
  
 END OF COMMENTS:
  