| 2005-08-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04120942 | | | ADD: 2010 PONCE DE LEON | | | CONT: TAYCON | | | TEL: (561762-0606 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | PRODUCT APPROVALS | | | 1) THE FL COVERSHEET FOR PGT FIXED | | | WINDOWS WAS SUBMITTED BUT NOT THE NOA. | | | | | | 2) THE SAAME HOLDS TRUE WITH THE PGT | | | MULLIONS ONLY THE COVERSHEETWHILE THE | | | REPORT INDICATES VAARIOUS NOA'S ARE | | | COVERED WITHIN THIS REPORT. | | | | | | 3) UNDER THE GARAGE DOOR REPORT | | | HIGHLIGHT OR INDICATE WHICH DOOR OR | | | SERIES YOU ENTENDTO USE? | | | | | | 4) STEEL ROOF PANELS ALSO INDICATE WHICH | | | SYSTEM INSULATED OR NOT? IF USING THE | | | NONINSULATED SYSTEM THE SYSTEM | | | LIMITATION OF A -60 MAXIMUM DESIGN | | | PRESSURE. YOUR ENGINEER CALCULATED AN | | | END ZONE PRESSURE OF -54.1 BUT USING THE | | | TRIBUTARY AREA OF 55 SQ FT. HE NOTES THE | | | END ZONE IS 3'. 3'X3'=9 SQ FT. AGAIN THE | | | | | | TABLES IN 1606.2B INDICATE A -68.1 WHICH | | | WILL REQUIRE ENHANCED FASTENING BY YOUR | | | ENGINEER ONLY FOR ZONE 3. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|