| 2005-06-14 00:00:00 | ************UNSAT 2ND REVIEW ******* |
| | |
| | *************************************** |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE SOME NOTES ARE NOW N/A DUE TO |
| | CHANGES IN DESIGN. |
| | PLEASE SEE MANY NEW NOTES DUE TO CHANGES |
| | ON PLANS. |
| | PLEASE SEE THE FIRST SET OF NOTES ARE |
| | TAKEN DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | 1)NOTE: UNABLE TO VERIFY: PLEASE SEE |
| | PERMIT APPLICATION COULD NOT BE LOCATED |
| | IN PLANS/PRODUCT APPROVALS/ PACKAGE |
| | RESUBMITTED. |
| | PLEASE SEE BLDG REVIEW COMMENTS |
| | PERTAINING TO THE NOTING OF "TOWNHOUSES" |
| | ETC. |
| | |
| | 2)NOTE: NOTE #2 N/A SEE NEW NOTES. |
| | |
| | 3)NOTE: NOTE #3 N/A SEE NEW NOTES. |
| | |
| | 4)NOTE: NOTE #4 N/A SEE NEW NOTES. |
| | |
| | 5)NOTE: NOTE #5 N/A SEE NEW NOTES. |
| | |
| | 6)NOTE: NOTE #6 N/A SEE NEW NOTES. |
| | |
| | 7)NOTE: NOTE #7 N/A SEE NEW NOTES. |
| | |
| | 8)NOTE: NOTE #8 N/A SEE NEW NOTES. |
| | |
| | 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE |
| | NEW NOTE ADDED TO E-2 WHICH MENTIONS A |
| | "C" AND "A" UNIT(S). ARE THESE THE SAME |
| | AS A1,ETC AND C1 ETC?? (MISPRINT)? |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE #12 NO, PLEASE SEE |
| | PREVIOUS NOTES. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 NO, PLEASE SEE SECOND |
| | SECTION OF THIS PREVIOUS NOTE. |
| | PLEASE KNOW THAT POOL IS TO BE A |
| | SEPARATE PERMIT. |
| | PLEASE SEE FIRST SECTION OF THIS |
| | PREVIOUS NOTE WAS ADDRESSED BY REMOVING |
| | ALL "SITE LIGHTING" POLES FROM SCOPE OF |
| | WORK AND PLANS. SEE E-1. |
| | |
| | 15)NOTE: NOTE #15 OK. #'S ADDED. |
| | HOWEVER PLEASE SEE ONE SET (SHEETS |
| | A1.1.0 AND A1.2.0 CONTAIN SEALED |
| | PHOTOCOPIES OF ARCH'S SIGNATURE. PLEASE |
| | SEE FS 481.221 REQUIRES THE SIGNATURE TO |
| | BEAN ORIGINAL "WET' SIGNATURE. |
| | THIS IS ONLY A NOTE. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | *************************************** |
| | NEW NOTES: |
| | |
| | 1)NOTE: PLEASE SEE PENINSULAR GFI RECEPT |
| | SPACING MISSING ONE. PLEASE SEE 210.52C3 |
| | AND 4. "B1" SEC FLR. |
| | PLEASE SEE THE SEPARATION BY THE SINK |
| | SHOWN, REQUIRES ONE ADDITIONAL GFI. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULES FOR |
| | SOME UNITS INDICATE PANELS TO BE LOCATED |
| | IN LAUNDRY RMS, HOWEVER PLEASE SEE PLANS |
| | E-1ETC SHOW ALL PANELS LOCATED IN |
| | GARAGES. PLEASE CORRELATE |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULES |
| | INDICATING SOME A/C HEAT AS 10KW, |
| | HOWEVER LOAD CALCULATIONS, OCP , AWG DO |
| | NOT CORRELATE. IF INDEED 10KW, PLEASE |
| | SEE 424.3B FOR MIN OCP TO BE 125%. |
| | PLEASE ALSO SEE MIN AWG PER 310.16. |
| | 240.4 |
| | PLEASE BE SURE THIS CORRELATES WITH MECH |
| | PLANS ALSO. |
| | |
| | 4)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES A "NOTE 9" AT LOCATIONS FOR |
| | A/C UNITS, GATE MOTORS ETC, HOWEVER THE |
| | PANEL SCHEDULES DO NOT CONTAIN A "NOTE |
| | 9". ONLY SHOWS 1-8 |
| | |
| | 5)NOTE: PLEASE SEE PLANS ARE NOW BEING |
| | SUBMITTED WITH A COMPLETELY NEW DESIGN |
| | FOR ELECTRICAL SERVICE AND BLDG |
| | FEEDS/SERVICES ETC. |
| | UPON CONVERSATION WITH THE BLDG PLAN |
| | REVIEWER AND UPON REVIEWING ELECTRICAL |
| | PLANS, PLANS ARE NOW INDICATING EACH |
| | BLDG TO BE "SEPARATE".?? |
| | PLEASE SEE ELECTRICAL RISER DIAGRAM NOW |
| | INDICATES "TWO SEPARATE SERVICES" , ONE |
| | FOR EACH BLDG. HOWEVER, PLEASE SEE |
| | ELECTRICAL RISER DIAGRAM ALSO NOW SHOWS |
| | ONE SERVICE FOR HOUSE ELECTRICAL |
| | CROSSING OVER AND FEEDING OTHER BLDG. |
| | THIS IS NOT PERMITTED. 230.2, |
| | 225.30-225.36,230.32 ETC. |
| | |
| | PLEASE SEE FIRE ALARM/ SPRINKLER CONTROL |
| | PANEL IS SHOWN BEING FED FROM ONE HOUSE |
| | PANEL. DOES THIS PANEL FEED INTO BOTH |
| | "SEPARATE BLDGS"?IF SO, THIS SHALL NOT |
| | BE PERMITTED. |
| | |
| | PLEASE SEE PLANS APPEAR TO NOW SHOW CATV |
| | AND PHONE SERVICE COMING INTO ONE BLDG |
| | AND THEN FEEDING SECOND BLDG? PLEASE |
| | CLARIFY. EACH BLDG MUST BE FED BY |
| | SEPARATE SERVICES AND SHALL NOT CONTAIN |
| | ANY CROSS OVER OF ELECTRICAL SYSTEMS. |
| | |
| | 6)NOTE: PLEASE SEE LOAD CALCULATIONS. |
| | PLEASE SEE THERE ARE NUMEROUS AREAS |
| | WHERE LOADS HAVE NOT BEEN CARRIED |
| | THROUGH TO MAIN SERVICE LOAD |
| | CALCULATIONS AND SOME DERATING IS BEING |
| | TAKEN BEFORE IT IS PERMITTED. |
| | PLEASE SEE A/C LOADS, 65%, PLEASE SEE |
| | PREVIOUS NOTES PERTAINING TO THE |
| | CORRELATION OF KW HEAT LOADS FOR UNITS |
| | AND SOME BEING SHOWN AS 10KW? |
| | PLEASE SEE KVA AS SHOWN ON EACH PANEL |
| | SCHEDULE HAS NOT BEEN CARRIED DOWN TO |
| | BLDG SERVICE LOAD CALCS. PLEASE SEE EACH |
| | PANEL LOAD (KVA) HAS BEEN DROPPED BY A |
| | SMALL AMOUNT. PLEASE CLARIFY WHERE AND |
| | HOW THIS "DERATING" OR DROPPING OF LOAD |
| | IS PERMITTED UNDER THE NEC BEFORE MAIN |
| | BLDG LOAD CALCS? |
| | PLEASE SEE 220.32 |
| | PLEASE SEE MAIN SERVICE FOR NORTH BLDG |
| | SHOWS LOAD AFTER ALL DERATING AT 599A'S |
| | ON A 600A MLO SERVICE. PLEASE SEE LOAD |
| | AS FIGURED IN NEC WOULD SUBSEQUENTLY |
| | TAKE SERVICE LOAD OVER THE 600A RATING |
| | OF EQUIPMENT. |
| | PLEASE RE-FIGURE LOAD CALCULATIONS AS |
| | PERMITTED UNDER NEC 220 FOR HOUSE LOADS |
| | AND FOR MULTI-FAMLIY UNITS. |
| | |
| | 7)NOTE: PLEASE INDICATE ON RISER DIAGRAM |
| | THE OCP FOR EACH UNIT. IT APPEARS TO |
| | SHOW 200A METERS? WITH A NOTE AT UPPER |
| | CORNER OFEACH RISER INDICATING A 150A |
| | 22K AIC RATED BRKR TO EACH.PLEASE |
| | REVISED TO MENTION 150A OCP FOR ALL |
| | UNITS TYPICAL. |
| | |
| | 8)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO THE |
| | DESIGN PROFESSIONAL FOR REPEAT COMMENTS |
| | FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME AS A COURTESY. |
| | PLEASE SEE DUE THE THE REPEAT COMMENTS |
| | AND THE EXTEND OF ELECTRICAL CODE |
| | COMPLIANCE NOTES ON SECOND REVIEW, ONE |
| | SET OF ELECTRICAL PLANS ARE BEING |
| | RETAINED. |
| | |
| | 9)NOTE: PLEASE SEE ANY POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON THE ELECTRICAL SHEETS. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SEE ONE SET OF ALL OLD/VOIDED |
| | SHEETS FROM EACH TRADE SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE NOTE** A RESPONSE LTR |
| | CONTAINING PREVIOUS COMMENTS AND REPLIES |
| | FROM DESIGN PROFESSIONALS HELPS IN THE |
| | PROCESSING OF PLAN REVIEWS AND |
| | UNDERSTING OF CODE RELATED |
| | ITEMS/COMMENTS AND RESPONSES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESTITATE TO CALL. |
| | |