Plan Review Notes
Plan Review Notes For Permit 04120942
Permit Number 04120942
Review Stop B
Sequence Number 2
Notes
Date Text
2005-06-08 00:00:00BUILDING PLAN REVIEW
 PERMIT:04120942
 ADD: 2010 PONCE DE LEON AV
 CONT: TAYCON CONSTRUCTION
 TEL: (561)718-3045
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
  
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A1.1.0 BUILDING DATA, MISSING
 INFORMATION FROM TABLE 500, BUILDING
 TYPE VI, IS PROVIDED, UNPROTECTED IS
 PROVIDED, BUT THE DECLARATION FOR
 INCREASE IN HEIGHT, FOOTNOTE "H" IS
 MISSING, TO ACCOMADATE THE STORY
 INCREASE (3 STORY).
  
 2A) COMMENT # 1 FROM THE PREVIOUS REVIEW
 DEALS WITH THE REMOVAL OF THE WORDING
 "TOWNHOUSE OR TOWNHOMES", THIS
 TERMINOLOGY IS INDICATED ON THE SOILS
 REPORT.
  
 2B) SOILS REPORT INDICATES THAT THEY ARE
 FOR 200-212 SW 9TH AVENUE FT LAUDERDALE
  
 2C) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 2D) SOILS REPORTS ARE TO BE ORIGINALS
 WITH RAISED SEAL & SIGNATURES. PLANS,
 SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) COMMENT # 4 FROM THE PREVIOUS REVIEW,
 FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS, THE GENERAL PROJECT
 DATA REPORT IS A COPY WITH THE DESIGN
 PROFESSIONALS COPIED SIGNATURE.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) DEALS WITH THE COMMENT# 12 FROM THE
 PREVIOUS REVIEW, SEE 411.2.6 FOR
 OCCUPANCY SEPERATION REQUIRED FROM THE
 HABITABLE AREAS TO THE GARAGE (R2), THE
 DOOR SCHEDULE HAS WHITE OUT ON THE
 SCHEDULE FOR THESE DOORS, THE SECOND
 ISSUE IS FOR THE (1) HR RATED WALL PLANS
 INDICATE A "C" LABEL DOOR, TABLE 705.1.2
 INDICATES OPENING PROTECTIVES IN MINUTES
 AND HOURS, PLEASE CORRECT.
  
 5) COMMENT# 15 FROM THE PREVIOUS REVIEW,
 S-6 TRUSS ANCHORS REQUIRE LOAD
 REDUCTIONS, 1609.4.3, DETAIL "A",GOOD
 FOR 11,150 NOT 12,340 SEE 2005 USP
 CATALOG.
  
 6) COMMENT# 17 FROM THE PREVIOUS REVIEW,
 S-7 ROOF UPLIFT PRESSURES ARE STILL LOW
 USE TABLE 1606.2B , ROOF ANGLES > 10-30
 DEGREES, WITH MULTIPLIER FROM TABLE
 1606.2D "B" = 1.05 FOR 33.83' MEAN ROOF
 HEIGHT.
  
 7) COMMENT# 18 FROM THE PREVIOUS REVIEW,
 EITHER THE ARCH OR STRUC SHEETS (ELE)
 INDICATE THE POS & NEG PRESSURES FOR
 OPENINGS, INCLUDE ENDZONES AND INTERIOR
 ZONES, AND MULTIPLIER FOR 33.83 MEAN
 ROOF HEIGHT.
  
 8)COMMENT# 19 FROM THE PREVIOUS REVIEW
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)COMMENT# 20 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOORS THE TESTING REPORT
 FOR THERMA-TRU DOORS WILL REQUIRE
 LOCAL PRODUCT APPROVAL, THE
 MANUFACTURER IS TO FILL OUT THIS
  
 FORM.
 B) TRUSS ANCHORS: PROVIDE THE FLORIDA
 COVERSHEET FOR, FL 821.8, FL 815.11
 & FL 2620.6.
 C) ROOF ASSEMBLIES:PRODUCT SUBMITTED
 ENGLERT INC. LOW PRESSURE FOR ZONE# 3.
 DEPENDING ON WHICH APPLICATION WHICH
 NONE ARE MARKED AS TO WHICH WILL BE
 USED, MAY HAVE PRESSURE LIMITATION OF
 -52.5.
 THE SECOND ISSUE IS THE DESIGN
 PROFESSIONAL SPECIFIES A DIFFERENT
 MANUFACTURER ON THE ELEVATIONS.
  
 10)COMMENT# 23 FROM THE PEVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) NEW COMMENT, DEALS WITH THE POOL;
  
 11A) THE LOCATION OF THE POOL VS THE
 LOCATION AND CHANGE IN ELEVATION FOR THE
  
 BALCONY FOOTINGS. SEE1803.1.3
 EXCAVATION FOR ANY PURPOSE SHALL NOT
 EXTEND WITHIN 1 FT OF THE ANGLE OF
 REPOSE OR NARURAL SLOPE OF THE SOIL
 UNDER ANY FOOTING OR FOUNDATION, UNLESS
 SUCH FOOTING OR FOUNDATION IS FIRST
 PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 11B) ALSO DEALS WITH THE LOCATION OF THE
  
 POOL VS. LIVING ROOM WINDOWS. 424.17.1.9
 (1) POOLS AND SAFETY ALARMS.
  
 NOTE :REVERSED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  