| Plan Review Notes For Permit 04120942 |
| Permit Number |
04120942 |
|
| Review Stop |
B |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2006-06-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04120942 | | | ADD: 2010 PONCE DE LEON AV | | | CONT: TAYCON | | | TEL: (561)262-2113 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: STAIR SHOP DRAWINGS | | | ACTION: DENIED | | | | | | THE TOP SET OF WINDERS FAILED: | | | 1007.8.1 WINDERS SHALL HAVE A MINIMUM | | | TREAD DEPTH OF 6 INCHES (152 MM) | | | AT THE NARROW EDGE AND SHALL HAVE A | | | MINIMUM TREAD DEPTH OF 11 INCHES (279 | | | MM) AT A POINT 12 INCHES (305 MM) FROM | | | THE NARROW EDGE.WINDERS SHALL BE | | | PERMITTED TO BE USED AS A COMPONENT IN | | | THE MEANS OF EGRESS WITHIN A | | | DWELLING UNIT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|