Plan Review Notes
Plan Review Notes For Permit 04120942
Permit Number 04120942
Review Stop P
Sequence Number 1
Notes
Date Text
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECT SHALL SHOW THE CERTIFICATE
 OF AUTHROIZATION ON THE TITLE BLOCK.
 SEE
 61G1-16.004(2) & FS 481.219.
 2) SHT P-1 INDICATES UNITS C1 & C2, BUT
 NO PLUMBING FLOOR PLANS OR RISER
 DIAGRAMS ARE SUBMITTED. PLEAS CLARIFY.
 3) SHT P-3 WATER RISER DIAGRAMS. THE
 WATER HAMMER ARRESTORS ARE REQUIRED AT
 THE WASH MACHINE HOT AND COLD WATER, AT
 THE DISHWASHER, AND AT THE
 REFRIDGERATOR. THEY WILL BE LOCATED
 NEAR
 THE FIXTURE IN AN EFFECTIVE RANGE, NOT
 IN THE CEILING. SECTION 604.9, AND
 PDI-WH 201.
 4) SHT P-3 SANITARY RISER DIAGRAM. APT
 B1, 2ND BATH, THIRD FLOOR, SHWR/TUB NOT
 VENTED. SECTION 901.2.1.
 5) SHT P-4 FIXTURE SCHEDULE, W/M SHOWS
 A
 1-1/2" TRAP. MINIMUM 2" TRAP REQUIRED.
 TABLE 709.1.
  
  