| 2005-01-24 00:00:00 | DENIED: | | | 1.ENERGY CALCUALTIONS FOR MODEL A & C | | | INDICATE MULTI-FAMILY.ENERGY | | | CALCULATIONS FOR A UNIT SHOWS SINGLE | | | FAMILY.PLEASE CLARIFY.SEE ALSO | | | COMMENT #1 BY JIM WITMER, BUILIDNG PLAN | | | REVIEW. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS IN | | | ACCORDANCE WITH 2001 FBC(M)402.2 & | | | 402.2.1 OR TABLE 403.3. | | | | | | 3.AHU'S SHALL HAVE A MINIMUM OF 4" | | | CLEARANCE AROUND UNIT FOR CONSTRUCTION, | | | SEALING, INSPECTION AND MAINTENANCE. | | | 2001 FBC(M)603.1.3. | | | | | | 4. DRYER EXHAUST TERMINATION SHALL BE | | | NON-SCREENED BUT EQUIPPED WITH A | | | BACKDRAFT DAMPER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|