Plan Review Notes
Plan Review Notes For Permit 04120942
Permit Number 04120942
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-24 00:00:00DENIED:
 1.ENERGY CALCUALTIONS FOR MODEL A & C
 INDICATE MULTI-FAMILY.ENERGY
 CALCULATIONS FOR A UNIT SHOWS SINGLE
 FAMILY.PLEASE CLARIFY.SEE ALSO
 COMMENT #1 BY JIM WITMER, BUILIDNG PLAN
 REVIEW.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M)402.2 &
 402.2.1 OR TABLE 403.3.
  
 3.AHU'S SHALL HAVE A MINIMUM OF 4"
 CLEARANCE AROUND UNIT FOR CONSTRUCTION,
 SEALING, INSPECTION AND MAINTENANCE.
 2001 FBC(M)603.1.3.
  
 4. DRYER EXHAUST TERMINATION SHALL BE
 NON-SCREENED BUT EQUIPPED WITH A
 BACKDRAFT DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.