| Plan Review Notes For Permit 04120942 |
| Permit Number |
04120942 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-20 00:00:00 | 1) CONTRUCTION WORK IS TO COMPLY WITH | | | NFPA 241. | | | | | | 2) BUILDING ADDRESSES ARE REQUIRED. | | | | | | 3) SMOKE DETECTORS SHALL BE PLACED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | | | | 4) IS THE DOOR BETWEEN THE GARAGE AND | | | LAUNDRY RATED. NO RATING SHOWN ON DOOR | | | SCHEDULE. | | | | | | 5) ELECTRONIC SWITCHES ARE REQUIRED ON | | | THE FIRE LINE BACKFLOW DEVICES. | | | | | | 6) FIRE ALARM SYSTEM SHALL BE UL LISTED | | | FOR CENTRAL STATION SERVICE. | | | | | | 7) FIRE ALARM SYSTEM SHALL BE CLASS A OR | | | FULLY ADDRESSABLE. | | | | | | 8) WHAT IS THE INTERIOR FINISH FOR WALLS | | | AND CEILINGS CLASS A, CLASS B, OR CLASS | | | C. | | | | | | 9) FIRE EXTINGUISHERS ARE REQUIRED. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|